Air Cooled Chiller Condenser Maintenance

7 large air cooled chiller condensers maintained with 12 fans each

Air Cooled Chiller Condenser Maintenance

Air cooled chiller condenser maintenance at Maximus Chillers. The condensers in the picture are a row of 6. These are remote from a row of 6 chillers, located in a plant room in the building below. The chillers are 750 kw single screw compressors with a control panel located to the side of each. On this visit, the emphasis of the maintenance was scheduled as being to the condensers.

Fan Speed Controllers

The refrigerant for the systems is R134a, so to allow for the saturation of the refrigerant, 8 bar is the head pressure set point. This pressure corresponds to the desired condenser temperature of 36°. Subcooling of 6° to 8° is achieved during the nominal operation of the plant. Each fan speed controller runs the 12 condenser fans together. Other condenser designs where fans bang on forwards and backwards cause vibrations resulting in reoccurring leaks on the condenser. Chiller No. 2 had tripped during a “discharge override” system message. On inspection of No. 2 condenser- the fans speed inverter had tripped on “over temperature” alarm. The panel fan, which is the kind to cool computers, was found to be still trying to run but seized. This failure had caused the alarm on the inverter. The panel fan was replaced from the stock of parts in the on site stores. The chiller was reset and a detailed Tick Sheet was completed noting the occurrence of this fault on arrival.

0161 370 7193

service@maximuschillers.com

Contact Form

Air Cooled Chiller Condenser Wash Down Maintenance

Because of the large size of the plant, the customer had installed a fireman’s hose for the wash down of the condensers during air cooled chiller maintenance. This is located in the free space beneath the condensers. It is fitted to a portable buggy so it can be moved under each condenser. Setting the nozzle to the correct attitude, our engineer moved the buggy sideways, so as to rinse the condenser in the direction of the fins. The condenser was relatively clean as the on site maintenance engineers carry this task out as part of their scheduled maintenance.

Related Blogs:
Air Cooled Chiller Planned Maintenance

Water Chiller Maintenance

Process Chiller Maintenance Visit

Chilled Water System Maintenance

Air Cooled Chiller Maintenance

Centrifugal Chiller Maintenance

Industrial Chiller Maintenance

Read more about HVAC air coils on Wikipedia | Click Here


Air cooled chiller planned maintenance showing both economizers with solenoid valves and expansion valves

Air Cooled Chiller Planned Maintenance

An air cooled chiller planned maintenance visit for a long standing customer of ours. They have just signed up to another 3 year contract. We know at Maximus Chillers that if we want to keep our customers, we must continue to offer the Maximus Service. Maximus is Latin for the highest and the greatest.

Planned Maintenance for Air Cooled Chillers

Planned maintenance is essential for these air cooled chillers as they are critical plant. They feed a large conference room which is a major part of the end user’s business. They can’t afford to loose the conference room when there is an event on. There is redundancy in the plant, but the customer always makes sure that the issues highlighted on the planned maintenance are acted on promptly. Also, the chillers feed a water cooled condenser for a pack which cools £50,000 of products used during the conferences.

Air Cooled Chiller Oil Planned Maintenance

1mw of cooling across 2 air cooled chillers were undergoing planned maintenance. Our engineer noticed that the oil level was slightly below the sight glass on one of the 250kw Bitzer compressors. The machine had previously been extensively run tested to ensure no oil return issues were present. Therefore, he decided to adjust the level with the oil available onsite.

0161 370 7193

service@maximuschillers.com

Contact Form

Economiser

The economisers, in the picture, were tested to ensure the solenoids were opening when the program sent the run signal. The electronic expansion valves functioned correctly and subcooled the liquid further after the condenser.

Head Pressure Control

The head pressure control was functioning correctly, keeping a steady 8 bar of pressure across all stages of loading and water system temperatures. This is because these chillers use a fan speed controller for each system. The fans cut in at the minimum running speed, which prevents stalling and over heating. Also, all fans running together are more reliable. Fans fail on systems using relays or pressure switches as the higher pressure fans don’t often come on. When they do, moisture has ingressed into them causing them to fail.

Related Blogs:
R134a Chilling Plant Maintenance

Water Chiller Maintenance

Process Chiller Maintenance Visit

Chilled Water System Maintenance

Air Cooled Chiller Maintenance

Centrifugal Chiller Maintenance

Industrial Chiller Maintenance

Follow this link to read more | Carel cut phase speed controllers


Air cooled chiller maintenance of two white chillers with green compressors

Air Cooled Chiller Maintenance

Air Cooled Chiller Maintenance Bodger Watch

We carry out air cooled chiller maintenance at an office building in the North West. Chiller maintenance is usually very good, but this is bodger watch! The customer told us that there had been this guy who used to come who spent most of his time in the canteen- reading manuals on his laptop! Not even the manuals for that site either! You couldn't make it up could you? What kind of a chiller maintenance schedule is that? They said he used to fix everyone's bathrooms in the evening to make up his pay! This is bodger watch!

Air Cooled Chiller Maintenance

One of our engineers rang the office from a site we look after the other week. He was struggling to carry out the maintenance- the antifreeze dosing. He was advised to use his testing instrument to assess the level in the water system. He came back with the result- too much antifreeze. The customer uses a non industrial antifreeze even though the site is heavy industrial. This is because the price is narrowing between industrial and non industrial antifreeze which is not toxic.

0161 370 7193

service@maximuschillers.com

Contact Form

On Site Maintenance Engineer

The customer adding antifreeze is the usual course- it means their onsite engineer can keep on top of things. This onsite engineer was a little too keen though: he had been putting too much in.

Antifreeze Removal

Our pump out team was sent to site with their tanker and equipment. Then, the correct level of antifreeze was then charged into the system.

Clear Site

Last but not least, our engineer gave the machine a wipe down and the chiller location a sweep- good house husbandry costs nothing.

For the efficient running of your plant- choose Maximus Chillers.

Related Blogs:
R134a Chilling Plant Maintenance

Water Chiller Maintenance

Air Cooled Chiller Planned Maintenance

Process Chiller Maintenance Visit

Chilled Water System Maintenance

Centrifugal Chiller Maintenance

Industrial Chiller Maintenance

Visit Refcom for industry guidance and advice


Translate