Category Archives: Chiller Components

Blue ammonia chiller with panel open during chiller controls company visit

Chiller Controls Company

Having an effective chiller controls company saves money! We at Maximus Chillers can repair any fault and upgrade where necessary. Read below to learn more…

Non Condensables

One of the non condensables that is found in a chiller is air. It had got into the system of the chiller in the photo due to a poor repair having been carried out. The end user had tried to save money by using a cheaper company to carry out a change of the suction strainer. They had forgotten to purge the pipework of air, leak test, and then pull a vacuum.

High Subcooling

The ingress of air had caused a ‘high subcooling’ message to appear on the PLC display. The controls work out the subcooling by looking at the pressure transducer reading, in this example it was 14 bar. Then, the onboard comparator understands the pressure/ temperature relationship of the refrigerant which is ammonia. This gave the saturation point temperature of 39°C. Also, the temperature sensor reading on the condenser was 25°C. The 14°C difference between the two temperatures was the subcooling. The parameters in the controls trigger this message if the subcooling is more than 12°C.

Air Purging

Our engineer attended site to carry out air purging according to standard industry guidelines. Our Risk Assessment Method Statement outlined the necessary PPE that was needed when handling this refrigerant. It also outlined the training and certification required by our engineer to handle anhydrous ammonia.

Subcooling Readings

He then ran the system up and checked the subcooling readings again. The condenser pressure was now 11 bar which corresponds to a saturation temperature of 31°C. The condenser temperature was still 25°C, so the subcooling was now 6°C. This was now below the alarm trip out level.

Dalton’s Law of Partial Pressures

This gas law states that all gasses in a pressurised vessel will act as if they are on their own. Therefore, with the air that was in the system, the condenser pressure was 14 bar, then after the air purging it was 11 bar. This means that there was 3 bar of air sat on top of the liquid refrigerant in the condenser. The air was causing a false reading of subcooling and therefore triggering the fault condition.

0161 370 7193

service@maximuschillers.com

Contact Form

Electrical Problems

Another fault message which had occurred during the time we have maintained this machine was oil separator low temperature. The oil separator is the vessel, just visible, to the left of the panel in the photo. This alarm is critical to protect the screw compressor from running with cold oil which will cause an expensive failure.

No Heater Burn Out

The oil separator heater was found to be off despite the cold temperature of the oil. The obvious reason was that it had burned out. The breaker was found to be in the 'on' position and there was no electrical charring visible.

Ohms Checked by Chiller Controls Company

When our engineer checked the ohms readings, they were found to be okay and there was no short to earth.

Run Signal

It was found that the 3 phase contactor was not pulling in to bring the heater on. Therefore, the next thing our engineer checked was weather the controller was sending out the run signal. It was- with 24v coming from the controller and the light being lit on the display. Somewhere in between, there was a problem…

Blown Relay

After consulting the wiring diagram, our engineer traced the fault to a blown relay. This relay provides a step in between from the 24v coming from the controller, to the 240v coil on the oil heater contactor. Rainwater had ingressed through a screw hole in the back of the panel. It had dribbled to the location of the A1 coil terminal on the relay. Here, it had been ‘tracking’ a few volts to earth. This was sufficient to burn out the coil without blowing the fuse. A drying agent suitable for electrical components was used, then the hole was sealed using a compound. There was a spare relay of the same type in the panel, so it was a quick job to swap it out.

Monitoring by Chiller Controls Company

Having done this, the contactor pulled in and the oil heater came on. Balanced amp readings were recorded on all three phases of the heater and the oil started to warm up. The oil separator temperature sensor was monitored for an hour on the controller. When the oil temperature rose to above the trip out level of 46°C, the fault condition automatically reset and the chiller came back on.

0161 370 7193

service@maximuschillers.com

Contact Form

Software Upgrade by Chiller Controls Company 

We had also previously found that the controller software was too finicky- causing a lot of spurious trip outs. Therefore, we decided to design our own software and upload it. This is easy to do because the controller is Bejer Electronics. It is a blank control system which can be used for almost any chiller, or other application. Read below to find out how we did it…

Chiller Controls Company Reliability

We rationalised what the customer needed and developed an upgraded program which was much more reliable. Getting a chiller to settle down and cost the customer less money is what we at Maximus Chillers are all about.

Chiller Controls Company's Test Rig

The controller had been removed from the chiller and wiped of its program. Then, the finished program was uploaded to the controller and a test rig set up. This was to iron out any teething problems before sending it back out into the field.

Laptop Plug In

When our engineer attended site, he fitted the upgraded controller and plugged it into his laptop. All of the program settings can be adjusted on the controller without the need of a laptop by entering the correct passwords for the program level required. However, a laptop has a bigger screen and so multiple readings can simultaneously be monitored. This facilitated the commissioning process.

Chiller Controls Company Testing and Adjustment

The chiller was run tested under various load conditions to check its performance. Also, all the fault conditions were either simulated or tripped out on the chiller. This was so that the program could be put to the test and adjusted accordingly. There were minor problems with fault timers which were adjusted, one at a time, so that no spurious trips would occur.

Completion

After monitoring the chiller for the rest of the day, it was time to talk to the customer about the job and get a signature. This chiller is in South West Wales, so it is a long, but very scenic, drive back for whichever of our engineers attends site. Read more about chiller upgrade.

Related Articles:
Chiller Parts Supplier

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Screw Chiller Compressor Maintenance

Chiller Controls

Scroll Chiller Compressor Maintenance

Chiller Condensers

Centrifugal Chiller Compressor Maintenance

Reciprocating Chiller Compressor Maintenance

To read more about chiller control systems hit the Tag at the top of the page.

Read more about the controls used for chiller/ heat pump units at the Carel website | Click Here


Two blue open drive Vilter reciprocating chiller compressors being maintained in a plant room

Reciprocating Chiller Compressor Maintenance

Reciprocating chiller compressor maintenance for two low temperature ammonia chillers. Reciprocating means a forwards and backwards motion in a straight line. This is achieved by converting the circular motion of the crankshaft, into a linear motion using the connecting rods. The pistons are on the end of the con rods, which slide up and down inside the cylinder liners.

Piston Rings

There are two types of piston rings which are used:

Compression Ring

This is the upper ring and is designed to a high tolerance to prevent the refrigerant vapour from bypassing the piston.

Oil Ring

This is the lower ring and is designed to regulate the oil flow around the piston.

0161 370 7193

service@maximuschillers.com

Contact Form

Cylinder Head

The cylinder head is usually cast iron and serves as a pressure plate. It holds the valve gear and has passageways for the suction and discharge of the refrigerant. The discharge pressure varies according to the kind of refrigerant and application. For a 0°C saturation it can be as low as 7 bar on R134a, or as high as 30 bar on R410a. The discharge temperature is usually around 60°C to 80°C which is recorded on our detailed Tick Sheet during the maintenance.

Valve Gear

Helix springs or reeds are popular with this type of compressor. Wave springs are another design that can be seen in operation on our YouTube channel. The video uses a cut away view and the oil is depicted in yellow. These springs control the suction (intake) and the discharge (exhaust) of the refrigerant…

Suction

The suction valves have the least amount of failures because the refrigerant is cool, low pressure and is carrying oil.

Discharge

The discharge valves, however, can have heavy molecules of hydrocarbons collect on them in the form of carbon. This causes them to not seat correctly, resulting in a deterioration of compressor performance. The difference in pressure between suction and discharge, otherwise known as the compression ratio, is a check that we carry out during the maintenance. The pressure and temperature is higher on the discharge valves, so more stress is exerted on to them. Therefore, they have a reduced lifespan by comparison to suction valves.

Top Dead Centre

The piston needs to come as close as possible to the cylinder head to create the largest amount of compressed refrigerant. This is called the clearance space which is usually less than 0.5 mm.

Discharge Header Safety Spring

This spring is fitted into the cylinder head and allows the valve gear to lift when:
• Liquid refrigerant slugs back to the compressor due to poor heat exchange in the evaporator.
• An oil slugging condition occurs.
• Water is drawn around the system from a burst condenser or evaporator.
As a compressor cannot compress a liquid, the valve gear lifting prevents an expensive compressor smash up from occurring.

0161 370 7193

service@maximuschillers.com

Contact Form

Reciprocating Chiller Compressor Maintenance of Shaft Seal

The compressors in the photo are open drive. Each has a shaft seal which has two, mirror finish rubbing surfaces. One seal turns with the crankshaft and the other is stationary. We check the amount of oil that is seeping from the shaft seal on every visit. When we notice that the level in the oil bottle is too high, we arrange a visit to change the shaft seal. This can be done without disruption to your process, as the other compressors can be left running while we carry out the work.

Reciprocating Chiller Compressor Maintenance of Drives

This kind of compressor is usually driven by an in line electric motor, as in the photo. It can also be driven by ‘v’ belts from an electric motor which is located to the side of the compressor. The ‘v’ belts are checked during the visit to see if there are any cracks on the inside working surface. We replace these with the pre ordered spares that are on site at no extra charge. They are then re tensioned according to standard industry guidelines.

Reciprocating Chiller Compressor Maintenance of Crankcase

This is a cast iron housing that all of the above components fit into. It provides the necessary support and strength for the compressor to operate at its high temperatures and pressures. The crankcase heater keeps the oil at operating temperature during the off cycles. It is usually a bore type which pushes into a hole in the casting. We check for the correct operation of the crankcase heaters and replace them where necessary. This is another spare that is kept on site, so that a return visit is not needed.

Service Ports

These bolt on to the compressor crankcase. They can be positioned in various directions, depending on which way the suction and discharge pipes go. The compressor can be valved off when it is being worked on. These ports are used by engineers to attach their gauges during the maintenance. On each visit, we check the calibration of the system pressure transducers by checking them against our gauges.

Reciprocating Chiller Compressor Maintenance of Oil Pump

This is a gear type pump which is fitted to the end of the compressor crankshaft. The pump sucks the oil through a filter from the sump of the compressor. Then, it is discharged from the pump, down the crankshaft passageways to the connecting rods. From here it travels up the con rod passageways and out through the pistons to the cylinder liners. Here, it provides the essential lubrication between the pistons and the liners. According to the maintenance schedule, we periodically change the oil filters to ensure the optimum running conditions of your compressors.

MAXIMUS ADVANTAGE™

If a compressor smash up occurs and the compressor is found to be obsolete- don’t worry. We can adapt the compressor mountings and the pipework for a different compressor. This is part of what we call The MAXIMUS ADVANTAGE™ Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere.

People also like this page:
Centrifugal Compressor Remanufacturing

Related Articles:
Chiller Parts Supplier

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Screw Chiller Compressor Maintenance

Chiller Controls

Scroll Chiller Compressor Maintenance

Chiller Condensers

Centrifugal Chiller Compressor Maintenance

Chiller Controls Company

To read more about reciprocating chiller compressors hit the Tag at the top of the page.

Read more about reciprocating compressors on Wikipedia | Click Here

 


Boxed, shell and tube chiller condenser being lifted into a building with a crane

Chiller Condensers

Shell & Tube

The chiller condenser on a 2 MW centrif we look after had deteriorated over a long period of time. We had carried out tube cleaning and noticed that it had been extensively repaired in the past. There were a lot of damaged tubes that had been blanked off. This had reduced the useful surface area for heat exchange to occur. The chiller was experiencing a ‘discharge limiting’ condition which was causing it to back off to 54% capacity.

Air Cooled

Because of the difficulty to remove and replace the condenser from the plant room, the customer had explored the possibility of air cooled condensers. His idea was to fit the discharge and liquid piping up the side of the building and into the plant room. After considering this possibility, we decided to advise him against using air cooled condensers because it would take two, 16 fan ‘V’ types. This would have a footprint too big for the available space. We decided to use a crane to lift out the old condenser, then lift in the new one.

Pump Out

The old condenser was valved off from the rest of the system and the refrigerant was pumped into an 800 kg recovery vessel. This was one of 2 vessels in the plant room that had been there since the chiller was new.

0161 370 7193

service@maximuschillers.com

Contact Form

Lift Out for Chiller Condensers

The pipework was unbolted and the ancillaries removed. When it came to unbolting the condenser, some of the bolts were seized due to a long period of rusting. Some of them came loose by heating them with oxy-acetylene, the others were ground off with an angle grinder. We used a specialist lifting company to shift the condenser from the plant room and out to the lifting bay. They then attached slings to one end, manoeuvred that end of the condenser to the outside of the building, then attached slings to the other end. Rather them than me! Quite a dangerous operation, but it had been assessed when composing their Risk Assessment Method Statement. The condenser was lifted onto the back of an articulated truck and taken to a scrap yard for recycling. There was quite a lot of copper inside- so our customer got quite a good weigh in!

Lift In for Chiller Condensers

The new condenser, in the photo, was kept in its packaging during the lift up, so as to protect it from damage. Once it was in the building and near to the plant room, it was removed from the box and shifted the rest of the way with dollies. There was some difficulty getting it into its final location. This was because the old steelwork had to be cut back with a blow torch to make the new condenser fit. Also, with limited room and no gantry crane, the lifting company had their work cut out to manoeuvre it. Eventually, it was in location and we decided to call it a day.

Adapting the Pipework

This particular condenser was selected because it was similar in dimensions to the old one. The positioning of the refrigerant and water system pipework was similar too. That said, it was not an exact match. We called an industrial plumbing and welding company in to make the changes we needed. They measured up and built adaptors to bolt in between the condenser and the water system pipework. They cut back the new condenser discharge connection and welded a new flange on. This was so it could be bolted onto the existing discharge elbow from the chiller. The liquid pipe connection on the new condenser was in the same location, but came with a different thread. Therefore, this too was cut back and an adaptor fitting was welded into place.

0161 370 7193

service@maximuschillers.com

Contact Form

Ancillaries

The fittings on the new condenser were BSP and the fittings on the chiller were Flare. We carry an extensive range of fittings that go between BSP and Flare. We can go from male to female, female to male, male to male and female to female. We can step up and step down in size too. Using these fittings, we attached the high pressure switch and high pressure transducer. The wires for the liquid and discharge temperature sensors were extended. This was so they could reach the location of the pockets that were built into the new condenser. Then, we used a special heat transfer paste to get a good transmission of heat in between the sensors and the pockets.

F-gas Pressure Test

We then carried out a strength test and a pressure test in accordance with F-gas guidelines. This was witnessed at the beginning and at the end by the customer. A satisfactory outcome was achieved, so on to the next phase of the job…

Dehydration of Chiller Condensers

We needed to dehydrate the system and remove the nitrogen that was used in the pressure test. This is because nitrogen is a non condensable which will affect system performance. Our powerful vacuum pump was set up, then we left it running overnight. A 1.5 Torr vacuum was achieved, which was the same pressure as when the Torr gauge was fitted directly on to the vacuum pump.

Open the Valves and Test

After removing the vacuum pump, the recovered refrigerant was pumped back in, then the discharge and liquid valves were opened back up. Then, our engineer had a good look round for leaks. I know it had just been pressure tested, but we think it’s always a good idea to check again. This done, the water system pumps were started and the water temperature showed at 23°C on the controller. The set point for the chilled water was 6°C so this warm water was helpful as it gave us plenty of load to carry out the testing. The chiller went through a timer and then started up. It loaded steadily up to 100% with no dramatics- splendid!

Related Articles:
Chiller Parts Supplier

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Screw Chiller Compressor Maintenance

Chiller Controls

Scroll Chiller Compressor Maintenance

Centrifugal Chiller Compressor Maintenance

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

To read more about chiller condenser systems hit the Tag at the top of the page.

Read more about chiller condensers on The Engineering Mindset | Click Here


Grey centrifugal chiller compressor being maintained

Centrifugal Chiller Compressor Maintenance

Centrifugal chiller compressor maintenance keeps your critical plant up and running and your customers happy. The work can be scheduled to be carried out during factory shutdown, so as not to disrupt your production. We can also carry out this work to your compressors while the factory is in production. This is achieved by isolating the compressor that needs to be worked on when it is in an off cycle. The compressors on remaining machines can carry on running.

Tasks during Centrifugal Chiller Compressor Maintenance

Here are some of the tasks that we carry out…

Oil Changes

The oil becomes dirty over time by picking up contaminants that have formed in the system. Two of these contaminants are…

Acid

Compressor discharge is the hottest part of the refrigerant cycle. Acid can be formed from the refrigerant in this part of the system.

Refrigerant Types

A popular refrigerant for centrifs is R134a. Because it consists only of one kind of refrigerant, it does not fractionalise into different component refrigerants. This would be no good for a flooded system because one or more of the refrigerants would end up in the bottom of the evaporator and condenser. The remaining refrigerant would circulate and the whole plant would not function as it should. Refrigerants popular for other kinds of system are zeotropic HFC refrigerants. This means that the different component refrigerants have different boiling points- R407c is a good example.

Metal

White metal from the compressor and copper from the heat exchangers end up in the oil. They will eventually be caught by the system oil filters…

Oil Filter Change

After completing the above, now is a good time to change the filter as the compressor is valved off and has been broken into. It is also when an oil sample is taken depending on the schedule…

Oil Samples during Centrifugal Chiller Compressor Maintenance

Our oil samples are transported using our specialist kits which include the bottles and labels. This saves mix ups in our laboratory during the analysis.

Leak Rectification

The drawback of carrying out the above are leaks because the pressure has been pumped out of the compressor into another part of the system. The ‘o’ rings and shaft seal can now leak, this kind of failure can be rectified whilst still on site by the knowledge of our engineers.

0161 370 7193

service@maximuschillers.com

Contact Form

Oil Pre Lubrication

When the compressor starts, the oil pressure is built up first using an oil pump. This is so the internal components such as the high and low speed shaft are properly oiled before they start to rotate. They can run at 10,000 RPM and are very expensive to replace. Therefore, we check the oil pressure gauges and the system controls to ensure optimum ‘pre lubing’ of your compressors.

Volumetric Efficiency

The ratio between the volume actually compressed and the theoretical volume derived from compressor design calculations. This kind of compressor has a lower volumetric efficiency than positive displacement compressors. It is because the refrigerant is compressed off the tip of the rotating impellor or impellors. The refrigerant moves outwards in a circular path due to centrifugal force. A centrif more than makes up for this lower volumetric efficiency by the high mass and volume of the refrigerant that it circulates around the system.

Design 

The refrigerant is sucked from the evaporator into the centre of the impellor which is a disc of radial blades positioned to direct the refrigerant outwards. Due to the low differential of pressure, multiple stages of impellors are often arranged in series with the discharge being directed onto the suction of the next impellor. This is simple in design with less moving parts than some other compressor types. Modern centrifs can have magnetic, levitating bearings and so remove the need for oil in the system altogether. The faster the speed, the better the efficiency- so high speed rotation of the impellor is achieved at full load. The compressed refrigerant is discharged into the condenser.

0161 370 7193

service@maximuschillers.com

Contact Form

Electric Drive Centrifugal Chiller Compressor Maintenance

Most modern centrifs are driven by variable speed drives. This is for efficiency as the load can be exactly matched. Another reason for this is to soft start the compressor. 415v and 3.3kv are popular volt inputs, although other voltages can be made available by the onsite transformer.

Open

An open drive electric motor is the most popular design. It has the drawback, however, of needing a shaft seal which needs to be replaced at periodic intervals. This shaft seal is also prone to leaking refrigerant and oil.

Semi Hermetic

The photo is of a semi hermetic design of this compressor type. The motor is contained inside the suction housing and so has the benefit of being cooled by the refrigerant. No shaft seal is needed and therefore it has none of the associated maintenance drawbacks.

Steam Drive Centrifugal Chiller Compressor Maintenance

On oil rigs there can be an abundant supply of steam that can be used to drive the compressor. It is often used on multi stage compressors which are used for the liquefaction of natural gas. The steam goes through a turbine which is connected to a shaft- this drives the impellors. The steam flow and pressure can be tested and adjusted during the visit.

Woops Something Went Wrong

When you suffer a centrifugal compressor failure- don’t worry. You are in safe hands with the team here at Maximus Chillers. We have a team who can get the compressor out and lift it to the workshop on site, or transport it to our Head Office. We have another team who are experts in the remanufacturing of this kind of compressor. A fast supply chain is in place for delivery of the internal moving parts, gaskets and bearings. We are so confident that you will be happy with us- we offer a 12 month warranty on all of our compressor rebuilds.

People also like this page:
Centrifugal Compressor Remanufacturing

Related Articles:
Chiller Parts Supplier

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Screw Chiller Compressor Maintenance

Chiller Controls

Scroll Chiller Compressor Maintenance

Chiller Condensers

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

To read more about centrifugal chiller compressors hit the Tag at the top of the page.

Read more about centrifugal compressors on The Engineering Mindset | Click Here

 


Open chiller controls panel showing PLC, relays, contactors and wiring

Chiller Controls

Chiller controls can be remotely operated and monitored, but in this article, we will be looking at chillers operating in local.

Each chiller has a panel where the lead or the lag chiller can be switched from. They have N+1 redundancy built in, so one of two chillers will normally be in standby with the other one running. The chillers in the photo are equipped with kilowatt hour meters because the customer wants to monitor their efficiency. He has targets to meet and wants to gauge the effect that our maintenance has in reducing his energy costs.

Condenser Pressure

The condenser pressure control is external and stand alone from the panel.

Transducer

A transducer is fitted to the discharge pipe near to the compressor. This gives a 0 to 5vdc control signal to the fan speed controller which is bolted to the frame. There is a minimum and a maximum value on the transducer, so the FSC is programmed to work out the pressure from the voltage.

Fan Speed Controller

415v on three phases are the input to the FSC. It uses solid state thyristors to regulate the output to the fans. This is according to the demand received by the transducer. Solid state means that all the parts are electronic with no moving parts. Fan speed controllers are really good at extending the life of the fans. This is because all of the fans operate together- smoothly and reliably.

Chiller Controls Digital Inputs

There are three essential digital inputs to the controls of any chiller. All of them have a volt signal out to them, which returns back to the panel. If there is a fault- the volts drop out.

LP Switch

This protects the chiller from a low pressure condition. Compressor and evaporator failure would result, so this device is set below the running pressure of the system, but high enough to offer protection.

HP Switch

If the head pressure control mentioned above were to fail, this device would save the chiller from damage from excessive pressure in the system. Components or the pressure relief valve can blow causing a catastrophic refrigerant leak.

Flow Switch

This device detects a lack of flow in the water system. Serious system failure would result if this part is not maintained properly. It needs to be periodically tested and adjusted at regular intervals.

0161 370 7193

service@maximuschillers.com

Contact Form

Chiller Controls Analogue Inputs

The essential analogue inputs on a chiller are the Water In and the Water Out sensors. These are usually NTC (negative temperature coefficient) that is to say: if you hold one in between your fingers and warm it up- the resistance will start to drop off. They usually read in kilo ohms which can be read on a standard multi meter. The program looks at these two sensors and using an algorithm, it calculates the loading requirement of the compressor. They can read incorrectly, so a sensor offset function is available in the software for adjustment. This is just one of the many checks and procedures that we carry out during our maintenance visit.

Chiller Controls Relays

In the photo you can see wires from the various devices around the chiller, wired into a row of relays. These, in turn, are wired into the white relay board at the top. This relay board has several expansion boards linked into it which are held together with an electrical ribbon. Next, the relay board is wired into the PLC... 

Chiller Controls PLC

The reason for these steps in between a device and the PLC is for protection. Sensitive electrical components can be blown due to an earth shortage. At each stage there is a volt drop from 240v to 24v and then to 5vdc.The programmable logic controller is the nerve centre of the chiller. This is where all the inputs go to and where all the digital outputs are sent from. The controller on this chiller is Beijer Electronics- it comes blank from the factory. User keys to operate the chiller are positioned below the display. It can be programmed to run most chillers and indeed it is often seen in factories running anything. A laptop plugs into it and the software for the chiller is uploaded. On one visit, we found a fault with this controller. We bubble wrapped it and took it to our electronics laboratory at Head Office. The issue was easy to resolve- it was just dust tracking across the back of the PCB and so corrupting the program.

0161 370 7193

service@maximuschillers.com

Contact Form

Chiller Controls Digital Outputs

The main digital outputs on this chiller are:

Compressor Run Signal

240v is sent to the compressor starter contactors. There are three: Star (lower amps for a soft start) then a timer switches over to Delta (higher amps for a more powerful running of the compressor) On the other end of the compressor windings is the Line contactor. This contactor runs with both the Star and the Delta contactors.

Float Valve

This is a camber where the level of refrigerant which is coming in from the condenser is detected. The level is transmitted to the PLC, where the program sends a signal to the expansion valve. It opens to the correct degree according to the load on the chiller.

Slide Valve

The compressor can run at 0% with the slide valve shut. When load is sensed from the Water In and Water Out sensors by the controller- the slide valve opens up. The position of the slide valve is detected by a potentiometer. This is calibrated from a minimum to a maximum position. The signal is 4-20 mA which the controller translates into the position of the slide valve.

MAXIMUS ADVANTAGE™

Whatever the problem with the controls, we can find a solution to resolve it. With years of industry experience and a fast supply chain, we offer a service that is second to none. Being able to retrofit is part of what we call the MAXIMUS ADVANTAGE™ Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere.

Related Articles:
Chiller Parts Supplier

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Screw Chiller Compressor Maintenance

Scroll Chiller Compressor Maintenance

Centrifugal Chiller Compressor Maintenance

Chiller Condensers

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

To read more about chiller control systems hit the Tag at the top of the page.

Read more about Chiller Control Basics on the Engineering Mindset | Click Here


6 green Bitzer scroll compressors being maintained in a chiller

Scroll Chiller Compressor Maintenance

Here at Maximus Chillers, we carry out scroll chiller compressor maintenance to extend the lifespan and reduce downtime to your critical plant. This planning ahead is central to how we do things- we resolve small problems before they become big problems. Having the capability to do anything is part of what we call the MAXIMUS ADVANTAGE™ Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere.

How they Work

The refrigerant vapour passes in between two scrolls (spirals) One of these is fixed, the other orbits backwards and forwards against the fixed scroll using a swing link. This creates a series of crescent shaped gas pockets in between the scrolls. These gas pockets get smaller in size as the refrigerant travels from the suction at the edge, down the spirals to the discharge at the centre. It then leaves downwards through a port. There are check valves to prevent back feeding of refrigerant during off cycles when other compressors on the same system are still running.

Advantages

There are several gas pockets occurring at any one time through the scroll, therefore giving a smooth and continuous compression cycle. Other advantages are low internal friction resulting in a quiet operation and low vibration levels. These low vibration levels help to lower the occurrence of leaks around the compressor.

Oil Level during Scroll Chiller Compressor Maintenance

The correct oil level is noted on our detailed Tick Sheets for all of the compressors. This record helps with the diagnosis when things start to go wrong. We can look for a pattern where the level starts to drop off in the compressors on a particular system, then look at the other readings which may be the cause.

Oil Samples during Scroll Chiller Compressor Maintenance

At periodic intervals, we take oil samples which we analyse in our laboratory at Head Office in Droylsden. We look for white metal, coloured metal, refrigerant composition, acid and sludge. This means that we can notice, then resolve system issues before a costly compressor failure occurs.

Oil Changes during Scroll Chiller Compressor Maintenance

This kind of compressor is fitted with a service port for the draining and filling of oil. The correct procedure is followed due to system pressure being present inside. We then carry out the oil changes using our specialist oil handling tools. Our skilled engineers carry the correct PPE for the work being carried out. We also we provide Risk Assessment Method Statements for each job.

0161 370 7193

service@maximuschillers.com

Contact Form

Crank Case Heaters

In the photo you can see the silver band of the crank case heaters at the bottom of the compressors. They keep the oil at the required temperature so as to not cause compressor wear on start up. The heaters also have the effect of ensuring that the refrigerant cannot condense into liquid during cold weather. As a compressor cannot compress a liquid, compressor failure would occur. A normally closed contact on the delta compressor starter contactor usually runs the heater: it drops out when the compressor starts. The function of all of these heaters is checked on each maintenance visit.

Discharge Temperature

It is critical that the discharge temperature is not too high, as this is the cause of the refrigerant breaking down into acid and sludge as previously mentioned. The acid rots the insulation on the copper windings inside the compressor. When this has occurred, an electrical failure will result in the compressor, causing the fuses to blow and a fault condition on the chiller. Compressor swap out is the cure which is expensive and inconvenient. We take the discharge temperature readings during the maintenance so as to fault find the cause.

Suction Pressure

Adequate suction pressure is needed to ensure good oil return to the compressor and prevent low pressure trips. As the refrigerant entrains the oil around the system, a good mass flow rate is needed, or the oil will just ‘pool’ in the bottom of the evaporator. Poor oil return will result in a seized compressor. Therefore, particular attention is taken to the low pressure gauge by our engineers. System adjustments or recommendations are made to ensure the seamless operation of your plant. If system overhaul is required, a Quote will be submitted at the end of the visit.

0161 370 7193

service@maximuschillers.com

Contact Form

Compressor Holding Down Bolts

There are usually four of these on each compressor. They fit though a steel sleeve which, in turn, fits through a rubber mount. The whole assembly is bolted into the frame of the chiller. The function is to securely hold the compressor in place and to dissipate vibration. We check the tightness is correct with our torque wrenches and change the rubbers periodically. A compressor rattling around uncontrollably, especially during start up and stopping causes catastrophic leaks around the compressor. This usually leads to the whole, or the most part of the refrigerant charge being lost to atmosphere.

Motor Protection Module

A resistance sensor embedded in the compressor windings plugs into this module on the S1 and S2 terminals. The fault feedback to the controls is on the M1 and M2 terminals. The power supply to the module is on the L and N terminals. When the windings start to get hot, the module detects this after a pre determined level of resistance is reached. The M2 terminal opens and volts drop out to the relay board, then a lower volt control signal drops out to the controller. We check the sensor resistance and compare it to a chart to ensure it is within the allowable range on each visit.

Wire Tightening during Scroll Chiller Compressor Maintenance

We waggle the motor connectors and check for any cracking to the wires which may lead to an earth sort out. We tighten the wiring on the compressor starter contactors and check the condition of the contactor contacts. These become ‘splattered’ causing an uneven amount of amps to the compressor. This volt drop causes the contactors to fail and will eventually cause compressor motor failure. We change the contactor contacts from our range of parts at Head Office.

People also like this page:
Centrifugal Compressor Remanufacturing

Related Articles:
Chiller Parts Supplier

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Screw Chiller Compressor Maintenance

Chiller Controls

Centrifugal Chiller Compressor Maintenance

Chiller Condensers

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

To read more about scroll chiller compressors hit the Tag at the top of the page.

Read more about scroll compressors on Wikipedia | Click Here


Grey shell & tube chiller evaporator being maintained with centrifugal compressor above

Shell & Tube Chiller Evaporator Maintenance

With shell & tube chiller evaporator maintenance to be carried out- it was time to sign the permit to work and get going. There are 5 chillers in total, but 1 of the chillers had been dismantled by the previous company and is unlikely to run again. This left 4 flooded systems to be maintained while the factory was still in production. Therefore, it had been decided in the Method Statement that one chiller would be done at a time. The plant had been designed with N+1 in mind, as it is critical not to loose the process- causing a factory shutdown. This means that so long as 2 of the chillers are running, there will be no loss in production. With 1 chiller out of service and another being worked on, this left 3 chillers in operation. If 1 were to fail, then there would still be the minimum of 2 left running.

Hire Chillers

In the unlikely event that 2 of the 3 chillers left running were to fail, an action plan was in place to lift in 1 MW of hire chillers.

Pump Sets and Hoses

The hire chillers would come with 2 engineers to pipe the pump sets into the onsite water system. This water system has been designed with this in mind so ‘stab ins’ have been built into it with shut off valves for the connection of temporary hoses.

Vanes

The chilled water is close control with a critical 6°C to 8°C set point. The chillers in the photo are very good at achieving this close control as they use vanes on the inlet to the suction. These vanes can be adjusted from anywhere between fully closed, with a small amount of bypassing, to fully open.

0161 370 7193

service@maximuschillers.com

Contact Form

Buffer Vessel

The hire chillers, on the other hand would not be close control. They would be multiple system chillers with various stages of loading on each chiller. One 600 kW chiller and another 400 kW. Each of the chillers onsite are 1.3 MW, but as they never run at 100% the onsite maintenance manager agreed to the proposal. It is unlikely that this plan would be needed, but planning for it is critical. A 10,000 ltr buffer vessel was decided upon to make the hire chillers close control. The chillers discharge into the buffer vessel, then the water mixes around before returning back to the chillers. The process water too being discharged into the buffer vessel before returning to the process. The position of the inlet and outlet on both water systems being strategically decided upon to ensure a steady exchange of heat and a smooth water out temperature back to the process.

Valve off and Drain Down

The Water In and Water Out pipes were valved off and the contents of the evaporator drained down. There was no glycol or chemicals in the water system which made the job easy. Otherwise, the water in the evaporator would have to have been pumped into vessels for disposal.

End Plate Removal during Shell & Tube Chiller Evaporator Maintenance

The lift and shift team were on site to assist with the removal of the end plate. After the bolts were removed, they attached their lifting eyes and straps, then lifted the end plate to the side.

Evaporator Cleaning 

We have in our stores a specialist evaporator cleaning tool. After a period of time, the evaporator tubes become fouled with impurities picked up from the water system. Also, contaminants get in from the air into the water tower. The strainer has some effect, but thermal insulation builds up on the water side of the tubes. It prevents latent heat being absorbed into the fridge system from the process. After the cleaning process, the efficiency of the copper tubes was increased to the same level as when the chiller was new. This is part of what we call the MAXIMUS ADVANTAGE Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere. 

Reassembly after Shell & Tube Chiller Evaporator Maintenance

The seal was replaced from our range of seal sizes, on the shelf in our stores. The reassembly being the reverse of the strip down, the lift and shift team aligning the end plate for refitting on guide runners. It was then tightened to the correct torque setting. A little at a time, the water system valves were opened until full flow and water system pressure was achieved. No leaks occurred, so it was time to go on to the next phase of the job…

0161 370 7193

service@maximuschillers.com

Contact Form

Run Up after Shell & Tube Chiller Evaporator Maintenance

After bringing this chiller back online, it went through a timer, then loaded up steadily to 68%. The refrigerant system readings had been taken previously, so they were compared to the readings taken after the job. A lot more heat transfer being achieved with more latent heat being absorbed from the process.

Remaining Chillers

The above mentioned process was repeated to the remaining chillers one at a time. No issues were encountered and the whole job proceeded steadily to completion.

Compressor Loading

The load from the factory is very steady, so each time another chiller evaporator was cleaned, the row of chillers would unload slightly. They were running at 72% on arrival, then 68%, then 63% then 59%. This was demonstrated to the customer as a visual way of proving how we had improved the efficiency of his plant. Compressor unloading uses less electricity, so lower carbon emissions and a lower electricity bill are the direct result of our maintenance. Also, kilowatt hour meters are linked to the maintenance manager's computer for monitoring.

Shell & Tube Evaporator Chiller Maintenance Tidiness

As with all of our jobs, the work location of the chillers was left in a better condition than when we arrived. Any waste and unused items being recycled or returned to the stores on site or the stores at our Head Office. The chillers being wiped down and the end plates re painted. With regular maintenance, we at Maximus Chillers will take years off the life of your plant. It is not unusual for us to keep this kind of plant running for more than 50 years.

Related Articles:
Chiller Parts Supplier

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Screw Chiller Compressor Maintenance

Scroll Chiller Compressor Maintenance

Chiller Controls

Centrifugal Chiller Compressor Maintenance

Chiller Condensers

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

To read more about shell & tube chiller evaporators hit the Tag at the top of the page.

Read more about shell and tube heat exchangers on Wikipedia | Click Here


Green Bitzer screw chiller compressor with oil separator removed on bench in our workshop

Screw Chiller Compressor Maintenance

Open Drive Screw Chiller Compressor Maintenance

Open drive screw chiller compressor maintenance involves changing the shaft seal at intervals, or if it leaks. This kind of compressor is used with ammonia as this refrigerant corrodes the copper windings and the insulation. It is also used with most large HFC (hydrofluorocarbon) and HFO (hydrofluoroolefin) chillers.

Semi Hermetic Screw Chiller Compressor Maintenance

Because all of the components are internal, this kind of compressor needs less maintenance. It is most often used with smaller chillers running on HFC and HFO refrigerants. This is the compressor type featured in the photo.

Matched Helical Rotors

This kind of compressor design uses a matched pair of helical rotors. These are accurately machined so as to trap, then compress the refrigerant as it travels along the screw. Oil injection is used to create a seal between the rotors. The two rotors are different in shape: the male rotor is driven by the motor and usually has 4 lobes. The female rotor meshes with male and usually has 6 interlobe spaces. The cylinder casting around the rotors is equally important as it seals in the vapour along the screw. Both rotors are helixes with the male rotor moving more rapidly. This compressor design provides a continuous pumping action, rather than pulsating as with a reciprocating compressor. Another advantage of this kind of compression is that there is very little vibration. Indeed, you can place a coin, on its side, on top of the compressors we look after and it does not fall over. This lack of vibration helps to prevent refrigerant leaks around the compressor.

Single Screw with Gate Rotors

This kind of compressor design uses one main rotor, meshing with 2 star gate rotors. These are at right angles with the main rotor. The main rotor usually has 6 grooves.

0161 370 7193

service@maximuschillers.com

Contact Form

Screw Chiller Compressor Maintenance and Reliability

Both of these compressor designs are very reliable with a long bearing life. A maintenance free lifespan of 30 years for the bearings is not uncommon. It is quite common that the compressor will outlive the chiller. In the unlikely event of bearing wear, a characteristic is for there to be undue noise from the compressor at part load which goes away at full load. Higher oil temperature and an unsatisfactory oil analysis are also indicators.

Slide Valve

The capacity is seamless as it is regulated with a slide valve. A spring returns the valve to the unloaded position and a gear type oil pump gives above discharge pressure to load it. The oil pump is not for lubrication, it is just to give the valve enough force to slide with the discharge pressure acting against it. A slide valve potentiometer is fitted to a sliding rod on the end of the valve. It translates the movement along this rod into usually 4-20mA. This signal feeds back to the controller which converts it into a percentage loading reading.

Lubrication during Screw Chiller Compressor Maintenance

Pressures and temperatures are taken during the maintenance to ensure seamless operation. The oil sump is usually inside the base of the oil separator which is at discharge pressure. An oil return pipe is available from the oil sump to the suction side of the screw. Because of the pressure difference from discharge to suction, the oil naturally lubricates the compressor without any need of an oil pump. The oil lubricates the bearings and is injected with the refrigerant along the screw. This provides a seal between the rotors or gate rotors, it also lubricates the rotors to prevent excessive wear.

Oil Separator

The oil enters the oil separator after being discharged with the refrigerant from the compressor. This vessel is insulated so as to stop refrigerant condensing inside as it would in the condenser. An oil heater keeps the oil at the optimum temperature for the compressor. This heater also prevents liquid from forming in the oil separator during off cycles. A check valve on the outlet also prevents this from happening by stopping the migration of refrigerant from the condenser. As the oil sump is the oil supply to the compressor, a temperature sensor will make the program lock the compressor out, should the oil be too cold. This is usually because the main power supply to the chiller has been off during maintenance. The larger volume inside the oil separator slows the speed of the refrigerant so as to allow the oil to drop out. A common design is for the discharge to be directed to the top of the vessel, with a spiral going down to the sump. The oil falls out of the refrigerant vapour during this process. For additional oil recovery, the oil goes up through finer and finer layers of mesh. The oil sticks to this mesh and runs down into the sump.

0161 370 7193

service@maximuschillers.com

Contact Form

Oil Return

Small amounts of oil that have escaped the oil separator will end up in various vessels around the system. On smaller HFC systems there is less of a problem as the oil is entrained by the refrigerant, round the system and back to the compressor. In larger, flooded HFC systems, the oil mainly ends up in the bottom of the evaporator. For ammonia systems, the oil does not entrain with the refrigerant, so oil return devices must be used.

Eductor

This is a pot at the bottom of the vessel where the oil collects. At periodic intervals, discharge gas is blown across the top of the oil which has collected. This has the effect of picking it up and carrying it into the suction of the compressor.

Periodic Oil Changes

We at Maximus Chillers have the full range of refrigerant grade oil for all refrigerant types. It is part of what we call the MAXIMUS ADVANTAGE™ Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere. It is critical that the correct oil is selected otherwise compressor failure will result. During each maintenance visit, we make a note of the compressor run hours and carry out oil changes at the correct intervals.

Oil Analysis

We take oil samples which we analyse in our laboratory for signs of compressor wear, oil quality and contaminants. This way, we can prevent untimely compressor failure. If one of your compressors were to fail, however, we have a remanufacturing facility and a lift and shift team to get the job done fast! 

People also like this page:
Centrifugal Compressor Remanufacturing

Related Articles:
Chiller Parts Supplier

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Scroll Chiller Compressor Maintenance

Chiller Controls

Centrifugal Chiller Compressor Maintenance

Chiller Condensers

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

To read more about screw chiller compressors hit the Tag at the top of the page.

Read more about rotary screw compressors on Wikipedia | Click Here


Chiller compressor failure of blue Grasso in enclosure

Chiller Compressors

System Testing for Chiller Compressors

Chiller compressors fail often as a result of ineffective servicing and system testing. At Maximus Chillers, we carry out extensive tests during our visits to ensure that small problems are resolved before they become big problems. If we notice a reading starting to become abnormal, we can carry out the diagnosis and then remedy the problem. Some of the compressor readings we monitor are:

Temperature of Chiller Compressors

The suction, discharge, motor windings and bearing temperatures are recorded for comparison to previous visits. These are often available in the PLC for the chiller, or our engineer can take the readings with his test equipment. Problems with the oil cooler can be the cause of higher compressor temperatures, the system running outside of its nominal operating conditions is another reason. Magnetic drive systems have an advantage as they do not use oil.

Accelerometer

Portable vibration sensors are carried in of each of our company vehicles. This is an accelerometer to measure vibration. Along with other system readings, we keep an on going record of the vibration levels around the compressor. When internal components are coming out of alignment due to wear, this causes an out of balance condition in the compressor. This, in turn, causes a knock on effect- causing other components to go out of balance. Catching this condition early will prevent a compressor smash up resulting in the replacement of expensive internal components.

Oil Analysis for Chiller Compressors

Another way of preventing big problems from occurring is periodic compressor oil testing. Samples are taken, usually on alternate visits, which are sent off to a laboratory for analysis. The acid level is tested to provide pre warning of a potential compressor motor windings burn out. This is because acid in the compressor oil rots through the electrical insulation on the motor windings. The presence and quantity of white metal and yellow metal is analysed too. This is a window through to a component starting to wear inside the compressor.

0161 370 7193

service@maximuschillers.com

Contact Form

Screw

The compressor in the photo is a screw compressor. It operates with ammonia refrigerant. This refrigerant is usually used for low temperature applications, mainly associated with food production. This compressor, however, has a 1°C refrigerant saturation and is used to cool computer rooms. Common causes of compressor failure on this kind of compressor are:

Leaking Castings on Chiller Compressors

The various compressor components are sealed together using ‘o’ rings or paper gaskets. ‘O’ rings are especially prone to leaks due to work hardening and flattening of the sealing face. The system can be pumped down and the compressor valved off. Then, our lift and shift team can remove the compressor to our remanufacturing facility for strip down.

Leaking Shaft Seal

The mating surface of a shaft seal has a mirror smooth finish. This is to reduce friction and aid with a better seal. Over time, this starts to wear, causing an ineffective seal with a leak of refrigerant and oil. A service visit can be arranged to change the shaft seal on site. The shaft couplings can be split, the shaft seal can then be removed and replaced. A quick job, then the machine is up and running again.

Slide Valve Potentiometer

This is an electronic device with a slide attached to the moving compressor slide valve. The device has a start and an end position programmed into it during commissioning. The potentiometer converts the slide valve position, usually into a 4-20mA signal which is fed back to the chiller PLC. They are prone to reading out, or the reading being jammed in one position. This results in a trip out from the controls, as the controller is not able to determine the true position of the compressor slide valve. We have an off the shelf stock of slide valve potentiometers for the various compressor range. A service visit can be arranged to replace the part after diagnosis has been carried out. The controls operate the loading and unloading solenoid valves to change the position of the slide valve.

0161 370 7193

service@maximuschillers.com

Contact Form

Centrifugal

Centrifugal compressors are a very reliable kind of compressor but when they go wrong, they can go wrong in a big way. Compressor overhaul is expensive, this can be carried out onsite, or a better option is a lift and shift to our remanufacturing facility. Proximity sensors are usually fitted to monitor the distance between the impeller and the casting. This is an added protection along with the other sensors and transducers around the compressor.

MCS

We are on account with Micro Control Systems- an American company who specialise in building panels to order for specific chiller compressors. We easily fit this control system to any compressor to control the loading of the vanes in accordance to the available load from the process. The control panel has previously been fitted to other machines of the same model number, so any teething issues have already been ironed out. Maximus Chillers can achieve seamless operation of your plant.

Oil System for Chiller Compressors 

Newer centrifugal compressors are oil free so as to eliminate any of the service issues relating to oil. There are a substantial amount of compressors, however, that use oil to lubricate the bearings. This kind of compressor, if properly serviced, can last for 50 years. The oil system picks up impurities which are caught by various filters. These filters can be changed or cleaned according to the prescribed service schedule. Our engineers make sure that spares are ordered and kept onsite prior to a visit.

Cost Effective

Our visits and ongoing upkeep of your plant saves money. Money spent as a preventative measure saves so much more money in the long run. With competitive prices on specialist internal centrifugal compressor parts- Maximus Chillers completes the picture. When compressor failure occurs, you are in safe hands with years of industry experience invested in each of our engineers.

0161 370 7193

service@maximuschillers.com

Contact Form

Scroll

These are some issues affecting a scroll compressor:

High Discharge Pressure

With high discharge pressure, there is a corresponding increase in discharge temperature. This means that the compressor is operating beyond its recommended values. The cause of this is often a poorly maintained condenser. Especially on industrial chillers, there can have been gaps in the schedule where the condenser was not correctly serviced. This condition is often rectified easily by an onsite engineer by giving it a brush down. Where the fins are bent over- we carry a specialist tool to straighten them back out- how they came out of the factory. We also use different formulas of chemicals to rinse the various kinds of dirt from deep within the fins.

High Suction Pressure on Chiller Compressors 

Some chillers are used where very high water temperature can come back from the process if the chiller were to be off line for a short period. Usually, this happens in factories where certain industrial processes are being carried out. When the onsite engineers start the plant back up, the chiller experiences a high heat load to deal with.

MOP Expansion Valves

Maximum operating pressure expansion valves limit the pressure in the evaporator to a given level, regardless of the available heat load from the process. They do this by having a limited amount of liquid refrigerant in the bulb. When this runs out, the power element cannot push the orifice open any further- thus limiting the suction pressure. This is important to prevent scroll compressor failure as it prevents putting added strain on the compressor motor windings due to high suction pressure.

Oil and Refrigerant Shortage

Where there is a shortage in refrigerant, there follows a low oil level condition. The refrigerant mass flow rate carries the oil around the system and back to the compressor. This is greatly impaired when the chiller is short of gas. The oil cools the compressor and lubricates the shaft bearings. These bearings and other internal components wear down and seize causing failure. Maximus Chillers can put together a package to minimise chiller compressor failure.

People also like this page:
Centrifugal Compressor Remanufacturing

Related Articles:
Screw Chiller Compressor Maintenance

Chiller Parts Supplier

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Scroll Chiller Compressor Maintenance

Chiller Controls

Centrifugal Chiller Compressor Maintenance

Chiller Condensers

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

To read more about scroll chiller compressors hit the Tag at the top of the page.

Visit Wikipedia to read more about impellers which are used in centrifugal compressors | Click Here


Yellow oil drums, ammonia refrigerant cylinders and flammable flushing agent of chiller supplier

Chiller Parts Supplier

Chiller Parts Supplier of Compressors

Centrifugal

As a chiller parts supplier, all kinds of centrifugal compressors are remanufactured in our workshop. With an overhead gantry crane and specialist equipment to hand- Maximus Chillers completes the picture. We have a lift and shift team who are skilled at getting the compressor out of the most awkward locations. A variety of lifting equipment is used, including 3 phase electric hoists and trollies. Our team do this kind of work all the time, so they are accustomed to overcoming all the difficulties and obstacles.

Screw

Screw compressors are remanufactured on the bench. With compressed air and bearing tools- our skilled technicians are seasoned in high tolerance measurements. The bearing clearance and shaft run out are accurately measured and adjusted. This means that the useful life of the compressor is extended, often to beyond the lifespan of the chiller.

Scroll

We have a range of off the shelf Copeland compressors for a fast lead time on process chiller repairs. These can be sent to site on the day using our fast door to door supply chain. We have all the sizes of compressor available. The pipework and mountings can be adapted too. This means that if your compressor is a different make with a longer lead time- our compressor will be fitted and adapted to your machine- fast!

Chiller Parts Supplier of Condensers

Air Cooled

When the condenser on an air cooled chiller is in poor condition- our site survey team will attend to measure up for a new bespoke condenser. This is done free of charge and ensures that the new condenser will fit easily into the old chiller. The exact subcooling requirement of the old condenser is taken into account which is duplicated on to the new condenser. This means a like for like swap can take place even when the old condenser is obsolete.

Shell and Tube

This type of condenser is used on water cooled chillers. It is protected from contaminants by a strainer on the water system. We have these condensers built to order by our bespoke manufacturer. They are shipped to site on an overnight delivery, so we can get straight down to work in the morning. We therefore minimise downtime in the swap out of this part.

Chiller Parts Supplier of Evaporators

Shell and tube are the most popular type of evaporator for large chillers. The low temperature refrigerant is on the outside of the tubes in liquid form. The water is pumped through the tubes, releasing heat from the process and into the refrigerant. This is latent heat as the liquid refrigerant boils off into a vapour. Where the heat exchange does not greatly improve after cleaning, we recommend replacing this part.

0161 370 7193

service@maximuschillers.com

Contact Form

Vibration Eliminators

We have all of the sizes of anacondas on the shelf in our stores. This saves on the delivery time to site when your process is off due to the chiller. Maximus Chillers will get you up and running- fast! We can also fit flexible vibration hoses which achieve the same result as anacondas. Whereas two anacondas are fitted vertically and horizontally, only one, long vibration hose is needed.

Chiller Parts Supplier of Flushing Agent

When things go wrong, we stock a solvent based flushing agent which is blown through the system using nitrogen. The waste product is caught on the far end in drums that come with the kit. This is then returned to the suppliers for recycling.

Refrigerant Economizers

These are another term for a subcooler. If the refrigerant is further subcooled after the condenser- the system will run more efficiently. This part usually takes the form of a plate heat exchanger with an expansion valve providing the refrigeration effect needed to further subcool the remaining liquid.

Chiller Parts Supplier of Pressure Transducers

We can make temporary repairs to faulty pressure transducers using our test equipment. This will keep your plant running while the part arrives on site. Then we can get your chiller up and running with the correct readings in the controls. This will assist your onsite maintenance engineers in giving us useful readings when we are in communications over the phone.

Chiller Parts Supplier of Ammonia and HFC Refrigerant

A full selection of refrigerants are available including: anhydrous ammonia, R407c, R134a and R410a. These refrigerants come in small 12kg, midi 26kg, large 56kg and bomb 800kg sizes. Our vehicles are equipped with tail lifts and lifting gear to facilitate delivery. We can therefore arrange the delivery and collection of refrigerant at your site, free of charge, anywhere in the UK. For our overseas customers, we arrange the transportation from the local suppliers.

Chiller Parts Supplier of Oil

Low, medium and high viscosity oils in 5ltr cans and 20ltr drums are ready for shipping from our storage area. It is critical to select the correct grade of compressor oil as bearing wear and reduced service life will result. We take regular samples of this oil to see if things are starting to go wrong in the compressor. We can then nip these problems in the bud, giving you dramatic savings.

Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere- The MAXIMUS ADVANTAGE™

Related Articles:
Screw Chiller Compressor Maintenance

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Scroll Chiller Compressor Maintenance

Chiller Controls

Centrifugal Chiller Compressor Maintenance

Chiller Condensers

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

To read more about chiller evaporators hit the Tag at the top of the page.

Read more about the centrifugal vapour compressor at the Institute of Refrigeration | Click Here


6 large air cooled chiller condensers maintained with 12 fans each

Air Cooled Chiller Condenser Maintenance

The photo is showing air cooled chiller condenser maintenance being carried out by Maximus Chillers. 6 water cooled chillers are located in the plant room below. They are 750 kw single screw compressors with a control panel located to the side of each. On this visit, the emphasis was to carry out a thorough maintenance of the condensers.

Fan Speed Controllers

The refrigerant for the systems is R134a, so to allow for the saturation of the refrigerant, 8 bar is the head pressure set point. This pressure corresponds to the desired condenser temperature of 36°C. Subcooling of 6°C to 8°C is achieved during the nominal operation of the plant. Each fan speed controller runs the 12 condenser fans together. Other condenser designs where fans bang on forwards and backwards cause vibrations resulting in reoccurring leaks on the condenser. Chiller No. 2 had tripped during a 'discharge override' system message. On inspection of No. 2 condenser- the fans speed inverter had tripped on 'over temperature' alarm. The panel fan, which is the kind to cool computers, was found to be still trying to run but seized. This failure had caused the alarm on the inverter. The panel fan was replaced from the stock of parts in the onsite stores. The chiller was reset and a detailed Tick Sheet was completed noting the occurrence of this fault on arrival.

Air Cooled Chiller Condenser Maintenance Cleaning

Because of the large size of the plant, the customer had installed a fireman’s hose for the cleaning of the condensers. This is located in the free space beneath the condensers. It is fitted to a portable buggy so it can be moved under each condenser. Setting the nozzle to the correct attitude, our engineer moved the buggy sideways, so as to rinse the condenser in the direction of the fins. The condenser was relatively clean as the onsite maintenance engineers carry out this task as part of their monthly schedule.

0161 370 7193

service@maximuschillers.com

Contact Form

Design Considerations for Air Cooled Chiller Condenser Maintenance

The kind of condenser in this article is:

Multiple Row Tubing

3 Rows

It has tubing of ½” diameter which is 3 rows deep. Each pass starts at the discharge header which is at the inlet to the condenser, goes down to the far end, through a condenser end turn, back to the discharge end, through another condenser end turn and back again to the liquid pipe end. The heat removed from the condenser, per kg of refrigerant, is the heat content of the vapour as it leaves the compressor, minus the heat remaining in the liquid at the end of the condenser.

6 Rows

Some condenser designs are up to 6 rows deep. This allows a small footprint of space where there is not much room for the location of the chiller. The downside to this, is that the chiller engineer can often struggle to locate the exact location of a leak when it is deep into the coil. If a condenser is too small, it will cause a higher head pressure and reduce the life of the compressor. We can arrange the lift out and repair of deep row condensers in our workshop.

Finned

This condenser has aluminium fins which are pressed around the copper tubing. This increases the surface area of the condenser heat exchange medium and so increases the dissipation of heat. The same amount of heat delivered to a condenser from the compressor must also be rapidly removed. For this condition to be reached, enough head pressure will need to be built up so that the condenser temperature is at least 15°C above the ambient. This is why the same chiller can be picked up and shipped to the Middle East and still work. It will just run at a higher discharge pressure/ temperature. There will, however, be a loss in the coefficient of performance as the higher pressures will result in more electricity in, versus the same amount of refrigeration effect out.

Forced Convection Type

The fans mounted on the ducting provide this forced convection. The air is sucked through the bottom of the condenser, across the 3 rows of tubes, along the fins and up through the fans. The air flow is stable as it enters the fins so good heat transfer is achieved. As it leaves the fins at the top, there is lower heat transfer as the air is turbulent.

0161 370 7193

service@maximuschillers.com

Contact Form

Fan Replacement during Air Cooled Chiller Condenser Maintenance

Spare fans are available onsite for replacement when individual fans fail. As mentioned above, these condensers are controlled with FSC's which reduce the occurrence of leaks. As well as this, fan speed controllers increase the lifespan of the fans. Because all of the fans run together, they speed up and slow down steadily. When high pressure control switches are used, they are set at different pressures. This means that some of the fans never come on until the head pressure is too high. This is usually due to a blocked condenser, failed fans or a high ambient. Because the fans have not come on for a long time, they are often seized or have suffered water ingress from the rain. An onsite maintenance engineer is available to help with the lift out and lift in of the replacement fans.

Pressure Relief Valves

Each of these condensers is fitted with a pressure relief valve (PRV) It is fitted into the discharge pipe on the inlet to the condenser. This is so that if the fans and the HP switch were to fail, the dangerous levels of pressure in the system would be vented. It is unlikely, however, that the HP switch would fail as this is a very reliable part. A PRV being fitted is often the requirement of insurance companies. The testing or replacement being arranged at scheduled intervals.

To read more about air cooled chiller condensers click the Tag at the top of the page.

Related Articles:
Chiller Parts Supplier

Chiller Compressors

Screw Chiller Compressor Maintenance

Shell & Tube Evaporator Maintenance

Scroll Chiller Compressor Maintenance

Chiller Controls

Centrifugal Chiller Compressor Maintenance

Chiller Condensers

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

Read more about HVAC air coils on Wikipedia | Click Here


Translate