Air Cooled Chiller Maintenance

400 kw white chillers with panels open during air cooled chiller maintenance

Air Cooled Chiller Maintenance

A nice day to carry out air cooled chiller maintenance at a new site we have taken over in the South East.

News Article No.6

Our engineer attended site at around 9am with the risk assessment method statement having been sent in advance. A site survey was carried out to see if there were any additional risks. Should there have been any changes- the RAMS have a section for the additional risks and control measures. After gaining a permit to work, our engineer was issued with a security pass to access the chiller compound. Three chillers are located in the compound which feed air handlers for a critical application. Two of the chillers are multiple system, scroll compressor, air cooled chillers. The other is a single system screw chiller.

Program Settings During Air Cooled Chiller Maintenance

A complete download of the program settings is available in our engineer’s phone. This is to cross reference the settings, should one of them be accidentally changed by the maintenance engineers. Onsite engineers are the first port of call for chiller trip outs, with the responsibility to get the plant up and running. We offer real time assistance, over the phone from our Technical Support Desk and can send user manuals in PDF form, direct to their computer. The settings were found to be nominal, so a detailed analysis of the alarm history was carried out:

Alarm History During Air Cooled Chiller Maintenance

In reverse date order, the alarm history of all the systems was interrogated. There had been several system shut downs to carry out the periodic maintenance by the onsite personnel. The electricity having been shut down, there was a subsequent oil pre heating timer in the history too. On Chiller 2, System 1 however, there had been several low pressure trip outs. Our engineer decided to start the maintenance with this system by carrying out a full diagnosis of the low side of the refrigerant system:

0161 370 7193

service@maximuschillers.com

Contact Form

Superheat During Air Cooled Chiller Maintenance

The system runs on R410a refrigerant. This refrigerant has higher operating pressures in comparison with other HFC refrigerants. It has an efficient temperature range which can be seen on a pressure enthalpy chart. Below or above this range- the refrigerant loses efficiency and so has a lower coefficient of performance. The most common saturation point for this refrigerant is 0° which corresponds to a 7 bar suction pressure in the evaporator. Above this is the superheat of the refrigerant returning to the compressor. On this occasion there was found to be 26° of superheat and a suction pressure of 4 bar- close to the low pressure trip out. After careful diagnosis, our engineer decided to focus his attention on the expansion valve:

Thermostatic Expansion Valve

There are 4 forces acting on a TEV:

Liquid line pressure coming from the condenser.
Versus
Suction pressure down the equalising line from the far side of the evaporator. This compensates for the pressure drop across the evaporator and shows the true compressor side pressure.

Spring pressure acting upwards and closing the valve.
Versus
Bulb pressure forcing the valve open.

To reduce the superheat, the bulb should have forced the valve open. The refrigerant charge in the bulb acts upon the bellows to achieve this. The reason for the malfunction, on this occasion, was found to be the failure of the expansion valve orifice. It had become jammed- causing a shortage of refrigerant in the evaporator/ high superheat.

Latent Heat

Our engineer was carrying out the above fault finding with one compressor running and the other two being held off. This was to prevent a low pressure trip. Where chillers are left running with a high superheat condition, the reduced amount of latent heat causes a higher cost in electricity relative to refrigeration effect (COP) The refrigerant carries on superheating without absorbing latent heat- pointless and inefficient for a chiller.

Chiller Pump Down

For convenience, this chiller can be pumped down and valved off using the service valves. The evaporator can be worked on after breaking in procedures are carried out. Therefore, we have arranged for this to be carried out before fitting the new expansion valve parts. These chillers also have the ability to pump down the refrigerant on receiving a fault feedback from the electronic leak detector. This is an added measure to lower the environmental impact of refrigerant leaks.

0161 370 7193

service@maximuschillers.com

Contact Form

Subcooling During Air Cooled Chiller Maintenance

Cooling the refrigerant vapour down, through the latent heat phase and then subcooling the liquid down further. On System 2 of the same chiller, a subcooling issue was identified. 21 bar/ 36° saturation was normal for that system as defined by the fan speed controller. Now, the system pressure was higher at 28 bar/ 47° saturation, so our engineer decided to work out the subcooling. A very high reading of subcooling was recorded at 28° this was diagnosed to be due to non condensables in the refrigerant:

System Non Condensables

Non condensables are gases that will not condense, such as, air and nitrogen. If nitrogen is not vented properly and a deep vacuum then achieved, the gasses will remain in the refrigerant system. When calculating the subcooling, the readings work out incorrectly due the presence of the gasses. This can lead to false diagnosis. The remedy for the issue was to arrange a full refrigerant decant, pressure testing and dehydration, before charging with new refrigerant.

Efficiency

Having good subcooling values on a refrigerant system is critical to efficiency. Where there is no subcooling- the refrigerant has not fully rejected all the latent heat from the condenser. This can be seen when looking at a PH chart and plotting the pressures and temperatures. This heat remains in the refrigerant and adds to the system along with heat added from the compressor and heat from the process. This is another reason the coefficient of performance is reduced and so incurring increasing electricity costs for the plant.

Economizer

These chillers are also fitted with refrigerant economizers- one for each system. They work by diverting some of the refrigerant from the condenser, through a small expansion valve, then through a plate heat exchanger. The rest of the liquid refrigerant passes on the other side of the plate heat exchanger and so is further subcooled.

Related Articles:
Air Cooled Chiller Planned Maintenance

Water Chiller Maintenance

Process Chiller Maintenance Visit

Chilled Water System Maintenance

Centrifugal Chiller Maintenance

Industrial Chiller Maintenance

Air Cooled Chiller Condenser Maintenance

Glycol Chiller Maintenance

Chiller Maintenance Company

Chilling Plant Maintenance

To read more about air cooled chiller maintenance hit the Tag at the top of the page.

For further reading on chilled water visit Wikipedia | Click Here


Yellow oil drums, ammonia refrigerant cylinders and flammable flushing agent of chiller parts supplier

Chiller Parts Supplier

Chiller Parts Supplier of Compressors

Centrifugal Compressors

As a chiller parts supplier, all kinds of centrifugal compressors are remanufactured in our workshop. With an over head gantry crane and specialist equipment to hand- Maximus Chillers completes the picture.

Screw Compressors

Screw compressors are remanufactured on the bench. With compressed air and bearing tools- our skilled screw compressor technicians are seasoned in high tolerance measurements.

Scroll Compressors

We have a range of off the shelf Copeland compressors for a fast lead time on process chiller repairs.

Chiller Parts Supplier of Condensers

Air Cooled Condensers

When the condenser on an air cooled chiller is in poor condition- our site survey team will attend to measure up for a new bespoke condenser.

Shell and Tube Condensers

This type of condenser is used on water cooled chillers.

Chiller Parts Supplier of Evaporators

Shell and Tube Evaporators

This is the most popular type of evaporator for large chillers. The low temperature refrigerant is on the outside of the tubes in liquid form. The water is pumped through the tubes, releasing heat from the process into the refrigerant. This is latent heat as the liquid refrigerant boils off into a vapour.

0161 370 7193

service@maximuschillers.com

Contact Form

Chiller Parts Supplier

Vibration Eliminators

We have all the sizes of anacondas on the shelf in our stores. This saves on the delivery time to site when your process if off due to the chiller. Maximus Chillers will get you up and running- fast!

Flushing Agent

For when things go wrong… we stock a solvent based flushing agent which is blown through the system with nitrogen.

Refrigerant Economizers

These are another term for a subcooler. If the refrigerant is further subcooled after the condenser- the system will run more efficiently.

Chiller Parts Supplier of Controls

Pressure Transducers

We can make temporary repairs to faulty pressure transducers using our test equipment. This will keep your plant running while the part arrives onsite.

Chiller Parts Supplier of Ammonia and HFC refrigerant

A full selection of refrigerants are available in our stores including: anhydrous ammonia, R407c, R134a and R410a.

Chiller Parts Supplier of Compressor Oil

Low, medium and high viscosity oils in 5ltr cans and 20ltr drums are ready for shipping from our storage area.

Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere- The MAXIMUS ADVANTAGE™

To read more about chiller evaporators- click the Tag at the top of the page.

Related Articles:
Chiller Refurbishment Company

Chiller Refurbishment Supplier

R407c Chiller Condenser Retrofitting

Chilled Water System Condenser Repair

Chiller Compressor Failure

Read more about the centrifugal vapour compressor at the Institute of Refrigeration | Click Here


Air cooled chiller planned maintenance showing both economizers with solenoid valves and expansion valves

Air Cooled Chiller Planned Maintenance

An air cooled chiller planned maintenance visit for a long standing customer of ours. They have just signed up to another 3 year contract. We know at Maximus Chillers that if we want to keep our customers, we must continue to offer the Maximus Service. Maximus is Latin for the highest and the greatest.

Critical Air Cooled Chiller Planned Maintenance

Planned maintenance is essential for these chillers as they are critical plant. They feed a large conference room which is a major part of the end user’s business. They can’t afford to loose the conference room when there is an event on. There is redundancy in the plant, but the customer always makes sure that the issues highlighted on the planned maintenance are acted on promptly. Also, the chillers feed a water cooled condenser for a pack which cools £50,000 of products used during the conferences.

Air Cooled Chiller Oil Planned Maintenance

There is 1mw of cooling across the 2 chillers. Our engineer noticed that the oil level was slightly below the sight glass on one of the 250kw Bitzer compressors. The machine had previously been extensively run tested to ensure no oil return issues were present. Therefore, he decided to adjust the level with the oil available onsite.

0161 370 7193

service@maximuschillers.com

Contact Form

Economizer

The economizers, in the picture, were tested to ensure the solenoids were opening when the program sent the run signal. The electronic expansion valves functioned correctly and subcooled the liquid further after the condenser.

Head Pressure Control

The head pressure control was functioning correctly, keeping a steady 8 bar of pressure across all stages of loading and water system temperatures. This is because these chillers use a fan speed controller for each system. The fans cut in at the minimum running speed, which prevents stalling and over heating. Also, all fans running together are more reliable. Fans fail on systems using relays or pressure switches as the higher pressure fans don’t often come on. When they do, moisture has ingressed into them causing them to fail.

To read more about air cooled chiller maintenance click the Tag at the top of the page.

Related Articles:
R134a Chilling Plant Maintenance

Water Chiller Maintenance

Process Chiller Maintenance Visit

Chilled Water System Maintenance

Centrifugal Chiller Maintenance

Industrial Chiller Maintenance

Air Cooled Chiller Condenser Maintenance

Chiller Maintenance Checklist

Planned Preventative Chiller Maintenance

Chiller Maintenance Schedule

Air Cooled Chiller Maintenance

Chiller Maintenance Company

Chilling Plant Maintenance