Air Cooled Screw Chiller Maintenance

Two green screw compressors being maintained in an air cooled chiller

Air Cooled Screw Chiller Maintenance

We recently carried out air cooled screw chiller maintenance at a site we look after in the North West. The plant is described such because it uses two Bitzer screw compressors to create a pressure difference in the R134a refrigerant. The plant has been designed to be remotely operated…

Chiller Remote

This is a way of operating the chiller remotely. Instead of the end user having to walk up to the machine each day to check for faults (chiller local) the plant can be remotely operated and monitored.

Run Signal

The run signal to start the chiller is sent by a relay being energised in the BMS panel (Building Management System) in the plant room. When the chiller receives the run signal, it shows the chiller on message.

Fault Feedback

When the chiller develops a fault, the chiller energises a relay, sending a fault feedback signal to the BMS panel. This fault signal causes the run signal to drop out and a new run signal to be sent to the adjacent redundant system.

BMS Panel

The BMS panel runs contactors which bring the water system pumps on, it also receives analogue signals from temperature sensors on the water system. These inputs and outputs are wired into a PCB which converts them into a data signal. This signal is sent down a CAT 5 plug cable to the supervisor in the facilities management room in the building below.

Remote Monitoring During Air Cooled Screw Chiller Maintenance

A supervisor is a computer which has graphic monitoring of the chillers and the air handlers. The supervisor, is connected down a phone line to the BMS company. Often, the chiller is remotely operated and monitored from a laptop used by a BMS engineer working from home.

0161 370 7193

service@maximuschillers.com

Contact Form

Air Cooled Screw Chiller Maintenance Parts

With a comprehensive range of chiller parts available, off the shelf, for air cooled chillers- look no further than Maximus Chillers for all your chiller parts. We can also supply parts mostly same day. A specialist part on this chiller is the electronic expansion valve driver- this regulates the steps in the expansion valve to ensure correct superheat in the shell and tube evaporator. An electronic expansion valve driver is also available to regulate the expansion valve in the refrigerant economiser. This acts to subcool the refrigerant to ensure optimum system efficiency.

Diagnosis During Air Cooled Screw Chiller Maintenance

Should you need chiller diagnosis- one of our trained professionals onsite during the maintenance will identify the issue with his system test equipment.

To read more about air cooled chiller maintenance click the Tag at the top of the page.

Related Articles:
Air Cooled Chiller Planned Maintenance

Water Chiller Maintenance

Process Chiller Maintenance Visit

Chilled Water System Maintenance

Air Cooled Chiller Maintenance

Centrifugal Chiller Maintenance

Industrial Chiller Maintenance

Air Cooled Chiller Condenser Maintenance

Chiller Maintenance Checklist

Read more about remote monitoring and control on Wikipedia | Click Here


A chiller condenser retrofitting lifting operation outside in the compound

R407c Chiller Condenser Retrofitting

We recently undertook the job to carry out bespoke R407c chiller condenser retrofitting in the North West.

Rusted and Corroded Condenser

The old condenser looked alright on the surface- the fins were in good condition. The chiller condenser was 18 years old and when an attempt to repair a leak was carried out- the condenser leaked further along. This is because of the warming of rusted and corroded copper with an oxy-acetylene torch.

R407c Chiller 'V' Condenser Retrofitting

We arrived on site to measure up for the job. The ‘V’ chiller condenser being retrofitted was built to order. We manufactured an exact replica to the same specifications and sizes of the old one. The operating pressures and high pressure cut out limit were taken into account in the design and the use of materials.

0161 370 7193

service@maximuschillers.com

Contact Form

Lift Out of the R407c Chiller Condenser being Retrofitted

On the day of the lift and shift we isolated the panel and checked it was dead, then we removed the panel and laid it on it’s front. This was to access the rivets behind the panel. These rivets, the ones on the other end of the chiller and around the lid were removed using a tool. The fans were disconnected and removed to make the lid lighter to lift off. Then, we attached slings to the chiller condenser and lifted both halves of the 'V' out.

Lift In of the Chiller Condenser being Retrofitted

This part we did not want to get wrong as the R407c chiller condenser being retrofitted was brand new and did not have a mark on it. A reverse of the removal- it fitted perfectly just the same as the old one. With the lid lifted back on and the fans in- time for brazing then the pressure test.

Pressure Test, Dehydration and Recharge

The pressure test was satisfactory so our engineer put the system on vac for dehydration purposes and the removal of non condensables. After a deep vacuum was achieved the system was recharged and run tested. No issues were found.