Chiller Types

Example of chiller types: 2 grey containerised ammonia chillers with air cooled condensers on top

Chiller Types

In this article we will be exploring the various chiller types. They can be categorised according to: how the condenser is cooled, weather they use vapour compression or absorption and the required chilled water temperature…

News Article No.17

Air Cooled Chiller Types

This type of chiller uses the ambient air to cool the refrigerant in the condenser. Fans suck the air through the condenser fins and so exchanging heat energy from the refrigerant and into the air. They are particularly popular in the UK due to the low ambient temperatures. They are also used in the Middle East, but the higher ambient means that they run less efficiently. Read more by following this link Click Here

Water Cooled Chiller Types

This type of chiller uses a shell and tube condenser to remove the heat energy from the refrigerant. The refrigerant condenses from a gas and into a liquid on one side of the tubes. On the other side of the tubes, condenser cooling water is being pumped through and so absorbing latent heat from the refrigerant. The water flows up to a cooling tower where it cascades down through trays and into the sump. In the opposite direction, air is blown up through the cooling tower and so creating the required heat exchange. The cooled condenser water is then pumped back to the chiller. This kind of system is more often used with large capacity chillers. Read more by following this link Click Here

0161 370 7193

service@maximuschillers.com

Contact Form

Vapour Compression

Vapour compression is the most popular kind of chiller. An electric motor drives a compressor. The refrigerant is then discharged into the condenser where the heat energy is rejected from the refrigerant as it cools down into a liquid. It goes through an expansion valve where it drops in pressure and temperature. Then, the refrigerant goes into the evaporator where it boils off absorbing latent heat from the water being chilled. The refrigerant is then sucked back into the compressor. This is called The Basic Refrigeration Cycle and you can read about it in detail by following this link Click Here

HFC Chillers

HFC chiller refrigerants, such as, R407c were developed to replace refrigerants which contained chlorine. This is because chlorine was found to have caused a hole in the ozone layer. The downside to HFC refrigerants is that they have a high Global Warming Potential. That is to say that when they find their way into the atmosphere due to refrigerant leaks, their heat trapping qualities add to the greenhouse effect.

Ammonia Chillers

The photo is of two ammonia chillers with air cooled condensers on top. A steel braided refrigerant charging hose can be seen coming into the foreground of the photo. This refrigerant has a zero global warming potential and so is environmentally friendly. The downside to this refrigerant is that it is highly toxic and corrosive. Therefore, special procedures, equipment and training is required to handle it. Read more by following this link Click Here

Propane Chillers

Propane didn’t really catch on in the UK due to the higher initial cost of the chiller. It is, however, popular on the continent in countries such as Italy. The downside to this refrigerant is that it is highly flammable. Intrinsically safe equipment is required to handle the refrigerant and so aiding with a spark free environment. Read more by following this link Click Here

Absorption Chillers

This kind of chiller uses a heat source rather than electricity to drive the cooling process. It employs a chemical reaction between two substances, such as, lithium bromide and water. To read about these chillers in detail Click Here This type of chiller is a lot less efficient than vapour compression systems. The coefficient of performance is usually around 0.5, were as with a HFC chiller it is usually upwards of 4. Therefore, they are most often used where there is a surplus of waste heat being produced by a process, such as, in a power station.

0161 370 7193

service@maximuschillers.com

Contact Form

High Temperature Chiller Types

Laser cutters use a chiller which operates with a high temperature set point of around 25°C. The laser head and the oscillator need to be cooled to a very close deadband of usually around 0.2°C. If there is a problem with the chiller, the controls shut the laser cuter down to prevent expensive failures from occurring. Read more by following this link Click Here

Medium Temperature Chiller Types

Most chillers operate at this temperature which is used for a variety of applications including…

The Cooling of Buildings

The chilled water set point is usually around 6°C. Large capacity chillers are used which supply chilled water to the building. A plant room is located near to the chillers where a pump discharges into the chillers. The water system pressure is maintained using a pressurisation unit. A different pump is used to supply fan coils around the building. The fans blow air across the chilled coils and so cooling the spaces in the building. This heat exchange warms the chilled water which returns back to the chillers.

The Plastics Industry

Two popular ways of forming plastic are by using: plastic extrusion moulding machines and plastic injection moulding machines. Plastic granules or powder is melted down and forced through a die or into a mould. Chilled water is then used to control the cooling of the newly formed plastic to below its freezing point. Small chillers are used next to each of the plastic forming machines. Alternatively, large, centralised chillers are used to provide chilled water to the whole factory.

Low Temperature Chiller Types

Breweries are a good example of the use of low temperature chillers. The setpoint is often around -5°C with glycol being added into the water to prevent it from freezing. The water/ glycol solution is pumped around the jackets of stainless steel vats which are used to brew the beer. The fermentation process created by the yeast is temperature critical and so is controlled by the chilled water. Read more by following this link Click Here

Related Articles:
Air Cooled Chiller Maintenance

Chiller Condensers

Industrial Refrigeration Ammonia

Glycol Chiller Maintenance

Hit the Tags at the top of the page to navigate your way to our extensive library of further reading on this subject.

To watch a video from The Engineering Mindset about chiller types on You Tube | Click Here


Nitrogen cylinder and regulator with gauges attached for f-gas chiller leak testing

F-gas Chiller Leak Testing

Regulations

The regulations for F-gas chiller leak testing have been devised to reduce the environmental impact of HFC refrigerants. They are standardised regulations which are implemented across Europe. Now that we have left the EU, we will continue to be aligned with these regulations.

News Article No.14

Leak Test Frequency Required

The frequency of leak tests depends on the type and quantity of the refrigerant. For example, a system which runs on R134a, the frequency is:
• once every 12 months for a charge less than 3.5 kg.
• once every 6 months for a charge less than 35 kg.
• once every 3 months for a charge less than 350 kg.
All of our maintenance schedules far exceed these minimum requirements. This is because our customers require maintenance visits more often to ensure the efficient running of their plant.

Static Leak Detectors

These leak detectors must be fitted to systems with more than 500 tonnes of CO2 equivalent. For the refrigerants most commonly used in chillers this is:
• R410a 239 kg
• R407c 282 kg
• R134a 350 kg

Global Warming Potential

The GWP numbers below represent the amount of greenhouse effect each refrigerant has, by comparison with an equal mass of carbon dioxide:
• R410a 2,088
• R407c 1,732
• R134a 1,300

Now we have had a look at some of the regulations, let’s have a look at a day in the life of our engineers here at Maximus Chillers. Read below for three different examples of leak testing carried out in the field…

0161 370 7193

service@maximuschillers.com

Contact Form

Pressure Testing Following a Leak

In the photo a leak has just been brazed on the condenser. It is recommended in the industry to use a steel braided line with a ¼ turn valve. This is so that if a nitrogen regulator malfunctions, it can be valved off, instead of a system being filled with bottle pressure from the cylinder. For a small system, this could cause a catastrophic explosion. We decided, therefore, to use a small cylinder which would expand into the large volume of the chiller. Should this fault occur, the safe working pressure would not be exceeded. This was taken into account when writing our Risk Assessment Method Statement. The pressure was built up in stages until the test pressure was achieved. This was recorded on our Pressure Test Certificate and witnessed by the customer. The result of the pressure test 4 hrs later was satisfactory and also witnessed by the customer.

Follow up Actions

A return visit was arranged 2 weeks later to leak test the chiller again. Our engineer carried out a visual inspection of all of the parts of the refrigerant pipework. He then used an electronic leak detector to see if it went into alarm. All was okay, so he completed the F-gas Certificate and left it in the customer’s file.

Routine F-gas Chiller Leak Testing during Maintenance

On another site, we look after 6 air cooled MW chillers in a row outside a building at a petrochemical facility. Our engineer ran the systems up, one at a time, to 100% so as to show up any refrigerant shortages. He was looking at the subcooling and superheat values. Two of the systems had poor readings which alerted his attention to a potential leak. On one of the systems, the poor readings were found to be caused by a faulty expansion valve. On the other, he diagnosed that the chiller was running short of refrigerant. He then carried out an inspection and found signs of a leak on a liquid pipe, just after the filter/ drier. The system was locked off with the refrigerant valves closed either side of the leak. This was to prevent the refrigerant from carrying on leaking to atmosphere. Then, he sent a report into Head Office detailing the estimated refrigerant addition needed to replace the refrigerant lost. Refrigerant removal was not needed as the area of the leak had been valved off from the rest of the system. He also detailed the materials required for the job and the necessary labour time that would be needed.

0161 370 7193

service@maximuschillers.com

Contact Form

Looking for a Leak

There are a variety of methods that can be used to identify the location of a refrigerant leak. Here are some examples…

Ultrasonic F-gas Chiller Leak Testing

An ultrasonic leak detector uses a microphone on the end of a wand. This is connected to a battery and processing pack, which is where headphones are plugged into. The sensitivity can be adjusted on the processing pack until a good working level is found. The various components on the chiller can then be inspected to find an audible sound of a leak.

Electronic F-gas Chiller Leak Testing

Otherwise known as a sniff tester, the electronic leak detector is one of the most popular types of leak detectors. The battery can be recharged via the cigar lighter in a car, or can be recharged back at the office with a transformer plugged into the mains. The heated diode sensor and the filter can fail or need to be replaced, so replacement parts are available. The instrument needs to be calibrated to a no refrigerant atmosphere, then it takes samples of the atmosphere being tested. It compares the two atmospheres and looks for a difference. Most electronic leak detectors work with all HFC refrigerants.

Bubble Up F-gas Chiller Leak Testing

There are a variety of bubble up leak detection sprays that are available off the shelf. At Maximus Chillers we make our own leak detection solution in our laboratory at Head Office. We mix two chemicals together in the correct proportions. This solution is carried in sprayer bottles in the boot of each of our company vehicles. When looking for a leak, our engineers use it around the suspected areas of a leak. It is the best form of leak detection that we know, as it can find the smallest of leaks, right up to large leaks which are audible to the ear.

Related Articles:
Chilling Plant Service

Chilled Water System EEV Service

Water System Service of Evaporator

HFC Chiller Service

Process Chiller Vacuum Service

Chiller Breakdown

Chiller Fault Finding & Diagnosis

Chiller Commissioning

Air Cooled Chiller Condenser Testing

To read more about the f-gas chiller leak testing procedure hit the Tag at the top of the page.

Read more about checking F-gas equipment for leaks on the Government website | Click Here


Maximus Chillers sign outside our chiller maintenance company office

Chiller Maintenance Company

Diagnosis of Chillers

One of the most important parts of a chiller maintenance company is the diagnosis. If this is done wrong, the wrong parts are ordered and the return job goes wrong.

News Article No.7

For us at Maximus Chillers, it is imperative that we get the diagnosis right, so the return job goes easy. On a maintenance visit, a detailed Tick Sheet is completed with all the necessary readings and adjustments.

Chiller Maintenance Company Case Study

One of our engineers was on a maintenance visit recently and he found an electrical fault with a relay. An intermittent fault- so the most annoying to diagnose. The relay interlocks the compressor A1 run signal on the start contactor. The fault causing the relay to drop out was the high pressure condition. The high pressure switch was found to be in good working order with continuity back to the relay, so the relay was deemed to be not switching intermittently. The relay was changed with the available stock on site and the machine went back into seamless operation.

State of the Art Equipment

At Maximus Chillers we know that incorrect test equipment can lead to incorrect diagnosis. That’s why we have the highest quality equipment which is regularly inspected, replaced or calibrated. With a Fluke multimeter with fused leads- we diagnose the most complicated of problems. Sometimes a wiring diagram is not available, or the machine has been modified. Even wires disappearing into a conduit and ending up on the other end of the chiller can be traced and effectively diagnosed. You can rest assured that with the ongoing maintenance by Maximus Chillers- we will extend the useful life of any chiller.

Chiller Maintenance Company Technical Support Desk

For over the phone diagnosis, our contract customers enjoy the full benefit of our technical support desk. Faults are often something and nothing, or are just to do with how the machine was restarted. If we can get a chiller away over the phone, that saves us time and that saves you: the customer money too. Just part of what we call the MAXIMUS ADVANTAGE™ Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere.

0161 370 7193

service@maximuschillers.com

Contact Form

Expansion Valves

We at Maximus Chillers have a comprehensive range of expansion valves, on the shelf, in our stores at Head Office in Droylsden, Manchester. There are three commonly used types of expansion valve used on a chiller:

Pulse Expansion Valve

This is a simple design of a solenoid coil lifting a solenoid valve and opening the diaphragm in the expansion valve. This allows the refrigerant to pass from the high side of the system into the low side. A sensor either side of the evaporator feeds back to the controls. The controls work out the length of time the valve stays open and the length of time the valve stays closed. Quite a simple idea and quite reliable from our experience too. The replacement of parts are a straight swap.

Electronic Expansion Valve

Another type of valve we stock is the electronic expansion valve. Similar to the above, this valve uses a sensor either side of the evaporator to work out the superheat. Another method of working out the superheat is a sensor and a transducer. Either way amounts to the same thing: the controls work out the difference in temperature and saturation point. The mechanical part of the valve is a step motor which winds all the way shut when the chiller starts. This is so that the controls can register step 0. As the valve opens, the controls record the amount of steps. It therefore knows the position of the valve to regulate a close control of superheat.

Thermostatic Expansion Valve

A thermostatic expansion valve is a completely mechanical and stand alone part. The pressure in the bulb increases with temperature and so forces the valve open. We have the full range of orifices for the commonly used varieties of valve on the shelf. Each orifice is used for a different application, ranging from low temperature -40°C saturation, through medium temperature 0°C saturation, to high temperature 20°C saturation. High temperature applications include laser chillers- the secondary refrigerant cools the oscillator and the laser head.

HFC Refrigerant

HFC refrigerant is being phased down to 21% by 2030. This is in accordance with F-gas guidelines and the emission reduction measures as defined in the Kyoto Protocol. This refrigerant, however, still remains to be the most popular type amongst chillers, with new chillers coming off the production line charged with, most commonly, R407c and sometimes R410a. R134a is also a popular chiller refrigerant most commonly used in flooded centrifugal chillers. The more the phasedown starts to pinch, the more the incentive to use a lower GWP (global warming potential) drop in refrigerant. This extends the useful life of the chiller, therefore removing the need to build a new chiller, with the associated high amount of carbon emissions.

0161 370 7193

service@maximuschillers.com

Contact Form

Evaporators

Eddy current Inspections by Chiller Maintenance Company

At periodic intervals according to the maintenance schedule, the end plates are taken off the evaporators and the tubes are inspected. We have calibrated eddy current instrumentation to assess the integrity of the evaporator tubing. This equipment uses electromagnetic coils to produce eddy currents, the electrical impedance is then measured. It picks up any cracks, pitting or corrosion. The conclusions are mapped onto a chart showing the tubes which are likely to fail. These tubes can be taken out of operation to prevent catastrophic system failure in the future. The system can then be pressure tested in accordance with F-gas leak testing requirements to prove the integrity of the system. Just part of the joined up, forward thinking of Maximus Chillers.

Chiller Maintenance Company Lagging

On our maintenance visits, one of a long list of checks is to check the insulation and vapour seal. If the lagging is not in place correctly, moisture from the air forms as condensation on the steel shell. This is not visible, so the condition of the steel can deteriorate dramatically over time. Where the lagging is in good condition, industry guidance states that it should not be removed to inspect. Where the lagging is in poor condition, however, it should be stripped back to the location of a good seal to inspect the integrity of the shell. For low temperature glycol or brine applications, rapid deterioration occurs as the shell is defrosting and re freezing between production cycles or defrost cycles. We heat treat the steel to remove all the moisture, then grind off any rust, before adding a two kinds of specialist paint available for sale at Maximus Chillers. We then match into the old lagging for a good join with our off the shelf varieties of lagging. The lower the temperature of the application, the greater the thickness of the lagging supplied.

Related Articles:
Air Cooled Chiller Planned Maintenance

Water Chiller Maintenance

Process Chiller Maintenance Visit

Chilled Water System Maintenance

Centrifugal Chiller Maintenance

Industrial Chiller Maintenance

Air Cooled Chiller Condenser Maintenance

Glycol Chiller Maintenance

Chilling Plant Maintenance

Preventative Chiller Maintenance

To read more about chiller diagnosis hit the Tag at the top of the page.

For further reading on F-gas enforcement reforms visit RAC Magazine | Click Here


Yellow oil drums, ammonia refrigerant cylinders and flammable flushing agent of chiller supplier

Chiller Parts Supplier

Chiller Parts Supplier of Compressors

Centrifugal

As a chiller parts supplier, all kinds of centrifugal compressors are remanufactured in our workshop. With an overhead gantry crane and specialist equipment to hand- Maximus Chillers completes the picture. We have a lift and shift team who are skilled at getting the compressor out of the most awkward locations. A variety of lifting equipment is used, including 3 phase electric hoists and trollies. Our team do this kind of work all the time, so they are accustomed to overcoming all the difficulties and obstacles.

Screw

Screw compressors are remanufactured on the bench. With compressed air and bearing tools- our skilled technicians are seasoned in high tolerance measurements. The bearing clearance and shaft run out are accurately measured and adjusted. This means that the useful life of the compressor is extended, often to beyond the lifespan of the chiller.

Scroll

We have a range of off the shelf Copeland compressors for a fast lead time on process chiller repairs. These can be sent to site on the day using our fast door to door supply chain. We have all the sizes of compressor available. The pipework and mountings can be adapted too. This means that if your compressor is a different make with a longer lead time- our compressor will be fitted and adapted to your machine- fast!

Chiller Parts Supplier of Condensers

Air Cooled

When the condenser on an air cooled chiller is in poor condition- our site survey team will attend to measure up for a new bespoke condenser. This is done free of charge and ensures that the new condenser will fit easily into the old chiller. The exact subcooling requirement of the old condenser is taken into account which is duplicated on to the new condenser. This means a like for like swap can take place even when the old condenser is obsolete.

Shell and Tube

This type of condenser is used on water cooled chillers. It is protected from contaminants by a strainer on the water system. We have these condensers built to order by our bespoke manufacturer. They are shipped to site on an overnight delivery, so we can get straight down to work in the morning. We therefore minimise downtime in the swap out of this part.

Chiller Parts Supplier of Evaporators

Shell and tube are the most popular type of evaporator for large chillers. The low temperature refrigerant is on the outside of the tubes in liquid form. The water is pumped through the tubes, releasing heat from the process and into the refrigerant. This is latent heat as the liquid refrigerant boils off into a vapour. Where the heat exchange does not greatly improve after cleaning, we recommend replacing this part.

0161 370 7193

service@maximuschillers.com

Contact Form

Vibration Eliminators

We have all of the sizes of anacondas on the shelf in our stores. This saves on the delivery time to site when your process is off due to the chiller. Maximus Chillers will get you up and running- fast! We can also fit flexible vibration hoses which achieve the same result as anacondas. Whereas two anacondas are fitted vertically and horizontally, only one, long vibration hose is needed.

Chiller Parts Supplier of Flushing Agent

When things go wrong, we stock a solvent based flushing agent which is blown through the system using nitrogen. The waste product is caught on the far end in drums that come with the kit. This is then returned to the suppliers for recycling.

Refrigerant Economizers

These are another term for a subcooler. If the refrigerant is further subcooled after the condenser- the system will run more efficiently. This part usually takes the form of a plate heat exchanger with an expansion valve providing the refrigeration effect needed to further subcool the remaining liquid.

Chiller Parts Supplier of Pressure Transducers

We can make temporary repairs to faulty pressure transducers using our test equipment. This will keep your plant running while the part arrives on site. Then we can get your chiller up and running with the correct readings in the controls. This will assist your onsite maintenance engineers in giving us useful readings when we are in communications over the phone.

Chiller Parts Supplier of Ammonia and HFC Refrigerant

A full selection of refrigerants are available including: anhydrous ammonia, R407c, R134a and R410a. These refrigerants come in small 12kg, midi 26kg, large 56kg and bomb 800kg sizes. Our vehicles are equipped with tail lifts and lifting gear to facilitate delivery. We can therefore arrange the delivery and collection of refrigerant at your site, free of charge, anywhere in the UK. For our overseas customers, we arrange the transportation from the local suppliers.

Chiller Parts Supplier of Oil

Low, medium and high viscosity oils in 5ltr cans and 20ltr drums are ready for shipping from our storage area. It is critical to select the correct grade of compressor oil as bearing wear and reduced service life will result. We take regular samples of this oil to see if things are starting to go wrong in the compressor. We can then nip these problems in the bud, giving you dramatic savings.

Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere- The MAXIMUS ADVANTAGE™

Related Articles:
Screw Chiller Compressor Maintenance

Chiller Compressors

Air Cooled Chiller Condenser Maintenance

Shell & Tube Evaporator Maintenance

Scroll Chiller Compressor Maintenance

Chiller Controls

Centrifugal Chiller Compressor Maintenance

Chiller Condensers

Reciprocating Chiller Compressor Maintenance

Chiller Controls Company

To read more about chiller evaporators hit the Tag at the top of the page.

Read more about the centrifugal vapour compressor at the Institute of Refrigeration | Click Here


Yellow oil drums, ammonia refrigerant cylinders and flammable flushing agent of chiller supplier

Chiller Refurbishment Supplier

Maximus Chillers is an established chiller refurbishment supplier. Maximus means the highest and the greatest in Latin, so we pride ourselves in offering the highest and the greatest customer service and technical capability. There is never a job too big for Maximus Chillers- we are seasoned in following a problem through to the logical solution.

Chiller Refurbishment Parts Supplier

Any part is available to our contract customers. We have a worldwide supply chain of the best suppliers. This means any part or refrigerant can be sourced at your convenience. When a part is not available, a different part of the same design specifications is selected and usually delivered same day. By same day we mean: the part is loaded into a van- then driven to site!

Oil and Refrigerant

We keep a stock of oil, refrigerant and other materials in our stores- see picture. This provides you with 'round the corner' convenience to your factory or facility. Whatever kind of ammonia grade specialist oil you require- we have it on the shelf. With a comprehensive range of other chemicals and solvents- Maximus Chillers completes the picture.

0161 370 7193

service@maximuschillers.com

Contact Form

Chiller Refurbishment Diagnosis

Our engineers are in their comfort zone while carrying out diagnosis during chiller refurbishment- that is what they do best! Even when a fault involves wiring that disappears into a loom, down the other end of the machine, with no wiring diagram- Maximus Chillers can help. Usually, however, faults are obvious to our engineers or can be found easily.

Technical Support Desk

Our contract customers enjoy the full benefit of our global technical support desk. We offer real time technical support with manuals being sent electronically to site. Where a time difference is involved, we arrange a time convenient to both locations, or answer emails when the office opens in the morning. If we can talk you through over the phone, we can get you up and running with the minimal disruption to your process.

Related Articles:
Chiller Refurbishment Company

R407c Chiller Condenser Retrofitting

Visit the ASHRAE for Standards and Guidelines Under Continuous Maintenance


An R407c chiller condenser retrofit lifting operation outside in the compound

R407c Chiller Condenser Retrofitting

We recently undertook the job to carry out bespoke R407c chiller condenser retrofitting in the North West.

Rusted and Corroded Condenser

The old condenser looked alright on the surface- the fins were in good condition. The condenser was 18 years old, however, so when an attempt to repair a leak was carried out- the condenser leaked further along. This is because of the warming of rusted and corroded copper with an oxy-acetylene torch.

R407c Chiller 'V' Condenser Retrofitting

We arrived on site to measure up for the job. The ‘V’ condenser was built to order. We manufactured an exact replica to the same specifications and sizes of the old one. The operating pressures and high pressure cut out limit were taken into account in the design and the use of materials.

0161 370 7193

service@maximuschillers.com

Contact Form

Lift Out of the R407c Chiller Condenser being Retrofitted

On the day of the lift and shift we isolated the panel and checked it was dead, then we removed the panel and laid it on its front. This was to access the rivets behind the panel. These rivets, the ones on the other end of the chiller and around the lid were removed using a tool. The fans were disconnected and removed to make the lid lighter to lift off. Then, we attached slings to the chiller condenser and lifted both halves of the 'V' out.

Lift In

This part we did not want to get wrong as the condenser was brand new and did not have a mark on it. A reverse of the removal- it fitted perfectly just the same as the old one. With the lid lifted back on and the fans in- time for brazing then the pressure test.

Pressure Test, Dehydration and Recharge

The pressure test was satisfactory so our engineer put the system on vac for dehydration purposes and the removal of non condensables. After a deep vacuum was achieved the system was recharged and run tested. No issues were found.