Chiller Maintenance Company

Maximus Chillers sign outside our chiller maintenance company office

Chiller Maintenance Company

Chiller Diagnosis

One of the most important parts of a chiller maintenance company is the diagnosis. If this is done wrong, the wrong parts are ordered and the return job goes wrong.

News Article No.7

For us at Maximus Chillers, it is imperative that we get the diagnosis right, so the return job goes easy. On a maintenance visit, a detailed Tick Sheet is completed with all the necessary readings and adjustments.

Chiller Maintenance Company Case Study

One of our engineers was on a maintenance visit recently and he found an electrical fault with a relay. An intermittent fault- so the most annoying to diagnose. The relay interlocks the compressor A1 run signal on the start contactor. The fault causing the relay to drop out was the high pressure condition. The high pressure switch was found to be in good working order with continuity back to the relay, so the relay was deemed to be not switching intermittently. The relay was changed with the available stock on site and the machine went back into seamless operation.

State of the Art Equipment

At Maximus Chillers we know that incorrect test equipment can lead to incorrect diagnosis. That’s why we have the highest quality equipment which is regularly inspected, replaced or calibrated. With a Fluke multimeter with fused leads- we diagnose the most complicated of problems. Sometimes a wiring diagram is not available, or the machine has been modified. Even wires disappearing into a conduit and ending up on the other end of the chiller can be traced and effectively diagnosed. You can rest assured that with the ongoing maintenance by Maximus Chillers- we will extend the useful life of any chiller.

Chiller Maintenance Company Technical Support Desk

For over the phone diagnosis, our contract customers enjoy the full benefit of our technical support desk. Faults are often something and nothing, or are just to do with how the machine was restarted. If we can get a chiller away over the phone, that saves us time and that saves you: the customer money too. Just part of what we call the MAXIMUS ADVANTAGE™ Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere.

0161 370 7193

service@maximuschillers.com

Contact Form

Chiller Expansion Valves

We at Maximus Chillers have a comprehensive range of expansion valves, on the shelf, in our stores at our chiller maintenance company in Droylsden, Manchester. There are three commonly used types of expansion valve used on a chiller:

Pulse Expansion Valve

This is a simple design of a solenoid coil lifting a solenoid valve and opening the diaphragm in the expansion valve. This allows the refrigerant to pass from the high side of the system into the low side. A sensor either side of the evaporator feeds back to the controls. The controls work out the length of time the valve stays open and the length of time the valve stays closed. Quite a simple idea and quite reliable from our experience too. The replacement of parts are a straight swap.

Electronic Expansion Valve

Another type of valve we stock is the electronic expansion valve. Similar to the above, this valve uses a sensor either side of the evaporator to work out the superheat. Another method of working out the superheat is a sensor and a transducer. Either way amounts to the same thing: the controls work out the difference in temperature and saturation point. The mechanical part of the valve is a step motor which winds all the way shut when the chiller starts. This is so that the controls can register step 0. As the valve opens, the controls record the amount of steps and so opens and closes for a close control of the superheat.

Thermostatic Expansion Valve

A thermostatic expansion valve is a completely mechanical and stand alone part. The pressure in the bulb increases with temperature and so forces the valve open. We have the full range of orifices for the commonly used varieties of valve on the shelf. Each orifice is used for a different application, ranging from low temperature -40° saturation, through medium temperature 0° saturation, to high temperature 20° saturation. High temperature applications include laser chillers- the secondary refrigerant cools the oscillator and the laser head.

HFC Chiller Refrigerant

HFC refrigerant is being phased down to 21% by 2030. This is in accordance with F-gas guidelines and the emission reduction measures as defined in the Kyoto Protocol. This refrigerant, however, still remains to be the most popular type amongst chillers, with new chillers coming of the production line charged with, most commonly, R407c and sometimes R410a. R134a is also a popular chiller refrigerant most commonly used in flooded centrifugal chillers. The more the phasedown starts to pinch, the more the incentive to use a lower GWP (global warming potential) drop in refrigerant. This extends the useful life of the chiller, therefore removing the need to build a new chiller, with the associated high amount of carbon emissions.

0161 370 7193

service@maximuschillers.com

Contact Form

Chiller Evaporators

Eddy current Inspections by Chiller Maintenance Company

At periodic intervals according to the maintenance schedule, the end plates are taken off the chiller evaporators and the tubes are inspected. We have calibrated eddy current instrumentation to assess the integrity of the evaporator tubing. This equipment uses electromagnetic coils to produce eddy currents, the electrical impedance is then measured. It picks up any cracks, pitting or corrosion. The conclusions are mapped onto a chart showing the tubes which are likely to fail. These tubes can be taken out of operation to prevent catastrophic system failure in the future. The system can then be pressure tested in accordance with F-gas leak testing requirements to prove the integrity of the system. Just part of the joined up forward thinking of this chiller maintenance company.

Chiller Maintenance Company Lagging

On our maintenance visits, one of a long list of checks is to check the insulation and vapour seal. If the lagging is not in place correctly, moisture from the air forms as condensation on the steel shell. This is not visible, so the condition of the steel can deteriorate dramatically over time. Where the lagging is in good condition, industry guidance states that it should not be removed to inspect. Where the lagging is in poor condition, however, it should be stripped back to the location of a good seal to inspect the integrity of the shell. For low temperature glycol or brine applications, rapid deterioration occurs as the shell is defrosting and re freezing between production cycles or defrost cycles. We heat treat the steel to remove all the moisture, then grind off any rust, before adding a two kinds of specialist paint available for sale at Maximus Chillers. We then match into the old lagging for a good join with our off the shelf varieties of lagging. The lower the temperature of the application, the greater the thickness of the lagging supplied.

Related Articles:
Air Cooled Chiller Planned Maintenance

Water Chiller Maintenance

Process Chiller Maintenance Visit

Chilled Water System Maintenance

Centrifugal Chiller Maintenance

Industrial Chiller Maintenance

Air Cooled Chiller Condenser Maintenance

Glycol Chiller Maintenance

Chilling Plant Maintenance

To read more about chiller diagnosis hit the Tag at the top of the page.

For further reading on F-gas enforcement reforms visit RAC Magazine | Click Here


400 kw white chillers with panels open during air cooled chiller maintenance

Air Cooled Chiller Maintenance

A nice day to carry out air cooled chiller maintenance at a new site we have taken over in the South East.

News Article No.6

Our engineer attended site at around 9am with the risk assessment method statement having been sent in advance. A site survey was carried out to see if there were any additional risks. Should there have been any changes- the RAMS have a section for the additional risks and control measures. After gaining a permit to work, our engineer was issued with a security pass to access the chiller compound. Three chillers are located in the compound which feed air handlers for a critical application. Two of the chillers are multiple system, scroll compressor, air cooled chillers. The other is a single system screw chiller.

Program Settings During Air Cooled Chiller Maintenance

A complete download of the program settings is available in our engineer’s phone. This is to cross reference the settings, should one of them be accidentally changed by the maintenance engineers. Onsite engineers are the first port of call for chiller trip outs, with the responsibility to get the plant up and running. We offer real time assistance, over the phone from our Technical Support Desk and can send user manuals in PDF form, direct to their computer. The settings were found to be nominal, so a detailed analysis of the alarm history was carried out:

Alarm History During Air Cooled Chiller Maintenance

In reverse date order, the alarm history of all the systems was interrogated. There had been several system shut downs to carry out the periodic maintenance by the onsite personnel. The electricity having been shut down, there was a subsequent oil pre heating timer in the history too. On Chiller 2, System 1 however, there had been several low pressure trip outs. Our engineer decided to start the maintenance with this system by carrying out a full diagnosis of the low side of the refrigerant system:

0161 370 7193

service@maximuschillers.com

Contact Form

Superheat During Air Cooled Chiller Maintenance

The system runs on R410a refrigerant. This refrigerant has higher operating pressures in comparison with other HFC refrigerants. It has an efficient temperature range which can be seen on a pressure enthalpy chart. Below or above this range- the refrigerant loses efficiency and so has a lower coefficient of performance. The most common saturation point for this refrigerant is 0° which corresponds to a 7 bar suction pressure in the evaporator. Above this is the superheat of the refrigerant returning to the compressor. On this occasion there was found to be 26° of superheat and a suction pressure of 4 bar- close to the low pressure trip out. After careful diagnosis, our engineer decided to focus his attention on the expansion valve:

Thermostatic Expansion Valve

There are 4 forces acting on a TEV:

Liquid line pressure coming from the condenser.
Versus
Suction pressure down the equalising line from the far side of the evaporator. This compensates for the pressure drop across the evaporator and shows the true compressor side pressure.

Spring pressure acting upwards and closing the valve.
Versus
Bulb pressure forcing the valve open.

To reduce the superheat, the bulb should have forced the valve open. The refrigerant charge in the bulb acts upon the bellows to achieve this. The reason for the malfunction, on this occasion, was found to be the failure of the expansion valve orifice. It had become jammed- causing a shortage of refrigerant in the evaporator/ high superheat.

Latent Heat

Our engineer was carrying out the above fault finding with one compressor running and the other two being held off. This was to prevent a low pressure trip. Where chillers are left running with a high superheat condition, the reduced amount of latent heat causes a higher cost in electricity relative to refrigeration effect (COP) The refrigerant carries on superheating without absorbing latent heat- pointless and inefficient for a chiller.

Chiller Pump Down

For convenience, this chiller can be pumped down and valved off using the service valves. The evaporator can be worked on after breaking in procedures are carried out. Therefore, we have arranged for this to be carried out before fitting the new expansion valve parts. These chillers also have the ability to pump down the refrigerant on receiving a fault feedback from the electronic leak detector. This is an added measure to lower the environmental impact of refrigerant leaks.

0161 370 7193

service@maximuschillers.com

Contact Form

Subcooling During Air Cooled Chiller Maintenance

Cooling the refrigerant vapour down, through the latent heat phase and then subcooling the liquid down further. On System 2 of the same chiller, a subcooling issue was identified. 21 bar/ 36° saturation was normal for that system as defined by the fan speed controller. Now, the system pressure was higher at 28 bar/ 47° saturation, so our engineer decided to work out the subcooling. A very high reading of subcooling was recorded at 28° this was diagnosed to be due to non condensables in the refrigerant:

System Non Condensables

Non condensables are gases that will not condense, such as, air and nitrogen. If nitrogen is not vented properly and a deep vacuum then achieved, the gasses will remain in the refrigerant system. When calculating the subcooling, the readings work out incorrectly due the presence of the gasses. This can lead to false diagnosis. The remedy for the issue was to arrange a full refrigerant decant, pressure testing and dehydration, before charging with new refrigerant.

Efficiency

Having good subcooling values on a refrigerant system is critical to efficiency. Where there is no subcooling- the refrigerant has not fully rejected all the latent heat from the condenser. This can be seen when looking at a PH chart and plotting the pressures and temperatures. This heat remains in the refrigerant and adds to the system along with heat added from the compressor and heat from the process. This is another reason the coefficient of performance is reduced and so incurring increasing electricity costs for the plant.

Economizer

These chillers are also fitted with refrigerant economizers- one for each system. They work by diverting some of the refrigerant from the condenser, through a small expansion valve, then through a plate heat exchanger. The rest of the liquid refrigerant passes on the other side of the plate heat exchanger and so is further subcooled.

Related Articles:
Air Cooled Chiller Planned Maintenance

Water Chiller Maintenance

Process Chiller Maintenance Visit

Chilled Water System Maintenance

Centrifugal Chiller Maintenance

Industrial Chiller Maintenance

Air Cooled Chiller Condenser Maintenance

Glycol Chiller Maintenance

Chiller Maintenance Company

Chilling Plant Maintenance

To read more about air cooled chiller maintenance hit the Tag at the top of the page.

For further reading on chilled water visit Wikipedia | Click Here


Yellow oil drums, ammonia refrigerant cylinders and flammable flushing agent of chiller parts supplier

Chiller Parts Supplier

Chiller Parts Supplier of Compressors

Centrifugal Compressors

As a chiller parts supplier, all kinds of centrifugal compressors are remanufactured in our workshop. With an over head gantry crane and specialist equipment to hand- Maximus Chillers completes the picture.

Screw Compressors

Screw compressors are remanufactured on the bench. With compressed air and bearing tools- our skilled screw compressor technicians are seasoned in high tolerance measurements.

Scroll Compressors

We have a range of off the shelf Copeland compressors for a fast lead time on process chiller repairs.

Chiller Parts Supplier of Condensers

Air Cooled Condensers

When the condenser on an air cooled chiller is in poor condition- our site survey team will attend to measure up for a new bespoke condenser.

Shell and Tube Condensers

This type of condenser is used on water cooled chillers.

Chiller Parts Supplier of Evaporators

Shell and Tube Evaporators

This is the most popular type of evaporator for large chillers. The low temperature refrigerant is on the outside of the tubes in liquid form. The water is pumped through the tubes, releasing heat from the process into the refrigerant. This is latent heat as the liquid refrigerant boils off into a vapour.

0161 370 7193

service@maximuschillers.com

Contact Form

Chiller Parts Supplier

Vibration Eliminators

We have all the sizes of anacondas on the shelf in our stores. This saves on the delivery time to site when your process if off due to the chiller. Maximus Chillers will get you up and running- fast!

Flushing Agent

For when things go wrong… we stock a solvent based flushing agent which is blown through the system with nitrogen.

Refrigerant Economizers

These are another term for a subcooler. If the refrigerant is further subcooled after the condenser- the system will run more efficiently.

Chiller Parts Supplier of Controls

Pressure Transducers

We can make temporary repairs to faulty pressure transducers using our test equipment. This will keep your plant running while the part arrives onsite.

Chiller Parts Supplier of Ammonia and HFC refrigerant

A full selection of refrigerants are available in our stores including: anhydrous ammonia, R407c, R134a and R410a.

Chiller Parts Supplier of Compressor Oil

Low, medium and high viscosity oils in 5ltr cans and 20ltr drums are ready for shipping from our storage area.

Any Chiller- Any Problem- Any Part- Any Refrigerant- Anywhere- The MAXIMUS ADVANTAGE™

To read more about chiller evaporators- click the Tag at the top of the page.

Related Articles:
Chiller Refurbishment Company

Chiller Refurbishment Supplier

R407c Chiller Condenser Retrofitting

Chilled Water System Condenser Repair

Chiller Compressor Failure

Read more about the centrifugal vapour compressor at the Institute of Refrigeration | Click Here


Yellow oil drums, ammonia refrigerant cylinders and flammable flushing agent of chiller parts supplier

Chiller Refurbishment Supplier

Maximus Chillers is an established chiller refurbishment supplier. Maximus means the highest and the greatest in Latin, so we pride ourselves in offering the highest and the greatest customer service and technical capability. There is never a job too big for Maximus Chillers- we are seasoned in following a problem through to the logical solution.

Chiller Refurbishment Parts Supplier

Any part is available to our contract customers. We have a worldwide supply chain of the best suppliers. This means any part or refrigerant can be sourced at your convenience. When a part is not available, a different part of the same design specifications is selected and usually delivered same day. By same day we mean: the part is loaded into a van- then and there- and driven to site!

Oil and Refrigerant

We keep a stock of oil, refrigerant and other materials in our stores- see picture. This provides you with 'round the corner' convenience to your factory or facility. Whatever kind of ammonia grade specialist oil you require- we have it on the shelf. With a comprehensive range of other chemicals and solvents- Maximus Chillers completes the picture.

0161 370 7193

service@maximuschillers.com

Contact Form

Chiller Refurbishment Diagnosis

Our engineers are in their comfort zone while carrying out diagnosis during chiller refurbishment- that is what they do best! Even when a fault involves wiring that disappears into a loom, down the other end of the machine, with no wiring diagram- Maximus Chillers can help. Usually, however, faults are obvious to our engineers or can be found easily.

Technical Support Desk

Our contract customers enjoy the full benefit of our global technical support desk. We offer real time technical support with manuals being sent electronically to site. Where a time difference is involved, we arrange a time convenient to both locations, or answer emails when the office opens in the morning. If we can talk you through over the phone, we can get you up and running with the minimal disruption to your process.

Related Articles:
Chiller Refurbishment Company

Chiller Condenser Retrofitting

Chiller Parts Supplier

R407c Chiller Condenser Retrofitting

Chiller Compressor Failure

Visit the ASHRAE for Standards and Guidelines Under Continuous Maintenance


Chilling plant service showing yellow top recovery cylinder with gauge line and sight glass fitted

Chilling Plant Service

Chilling plant service had been arranged because our customer had been having high pressure problems.

Transducer Required Chilling Plant Service

The 4-20mA transducer needed replacing as it was reading low by a long shot. Therefore, the PLC was not bringing the fans on as it should. The pressure in the high side of the system was getting up to 40 bar. This is because the refrigerant was R410a- it has a higher head pressure than other commonly used HFC refrigerants, such as, R407c. We ordered the replacement transducer which is fitted with a female fitting.

Chilling Plant Service Leaks

Our engineer concentrated his attention on the high side of the system to start with. Then, he found a leak on a fitting, a leak on the pressure relief valve fitting and a leak on the liquid line near the drier. A sealant was used for leaks on the fittings- they were removed, cleaned and refitted. The leak on the liquid line was re sealed by removing the section of pipe, removing any remaining solder, then the section of pipe was rebrazed.

0161 370 7193

service@maximuschillers.com

Contact Form

Pressure Test

The remaining parts of the system were leak tested then the plant was put on a pressure test to ensure the whole system was leak free. The pressure test was satisfactory and so the evacuation process could be started.

Evacuation Process 

Each of our engineers has a powerful vac pump to speed up the dehydration process. This means that a deep vacuum can often be pulled on the same day, instead of the usual overnight process. The nitrogen and other non condensables were removed quickly and the Torr gauge came down to the pressure where moisture was being removed. At this pressure, any moisture is forced to boil off around the system.

Recharging of the Chilling Plant Being Serviced

In the photo, the plant is being recharged at the end of the work. It is being recharged into the liquid side of the evaporator. All readings were okay when running the system and further leak tests were carried out at normal operating pressures.

Related Articles:
Global Chilled Water System Service

Chilled Water System EEV Service

Water System Service of Evaporator

Process Chiller Service

HFC Chiller service

Process Chiller Vacuum Service

Chiller Fan Deck Service

Packaged Chiller Service

Chiller Service Company

Chiller Breakdown

Read more about refrigerant reclamation by following this link to Wikipedia | Click Here


Chilled water system repair of condenser to a silver chiller with blue compressors

Chilled Water System Condenser Repair

Chilled Water System Condenser Beyond Repair

The repair of the condenser was required on this chilled water system because the previous company had been chasing leaks round in a circle. Therefore, the customer had decided to buy a new condenser. This was our first job with a new Contract, so we wanted to make a good impression.

Condenser Removal

There was no refrigerant in the system so our engineer cut the discharge and liquid line to the condenser. He then removed the rivets so the frame could be taken apart. Lifting equipment was fitted to the old condenser to aid the removal. Then, slings were fitted and a forklift truck removed the old condenser.

Condenser Replacement

Our engineer supervised the condenser replacement. He found that the new condenser did not fit correctly. The new condenser was 5mm thicker than the old one. It was decided to lift it back out and angle grind the frame to make more room. Once this was completed, the new condenser fitted correctly and was bolted in place.

0161 370 7193

service@maximuschillers.com

Contact Form

Pipework Repair

The pipework had to be repaired and brazed in. Then, the standard practice of a pressure test to ensure the integrity of the system.

The Evacuation Process

Having passed the pressure test, our engineer set up the vac pump and started the evacuation process. This is to dehydrate the system by pulling a vacuum of less than 2 Torr. Any moisture in the system will boil away and leave the system dry.

Recharge and Test Operation

The refrigerant is R410a. Our engineer put around half the charge in, then trimmed the remaining charge according to the superheat and subcooling values. He monitored the system for the rest of the day- looking for leaks as the plant was at operating pressures of 30 Bar. All was well, so the customer signed off the paperwork as he was pleased with the capability of our engineer.

Related Articles:
Air Cooled Chiller Condenser Maintenance

R407c Chiller Condenser Retrofitting

Chiller Compressor Failure

Read about air cooled condenser installation at the Institute of Refrigeration | Click Here


Translate