by Maximus Chillers | Oct 29, 2020 | Chilling Plant
We at Maximus Chillers carry out chilling plant maintenance in factories and facilities around the UK and overseas. HFC Refrigerants HFC (hydrofluorocarbon) chiller refrigerants were developed to be chlorine free. For a while they were seen to be the great new thing...
by Maximus Chillers | Jun 8, 2020 | Chilling Plant
On this chilling plant maintenance visit, particular attention was made to compressor loading. This was to ensure that the compressors are capable of operating at 100%. With summer now here- we want the plant capable of running at full capacity. Controller Loading...
by Maximus Chillers | May 17, 2020 | Chilling Plant
Prior to this chilling plant controls maintenance visit, another contractor had changed some of the settings and adjustments in the controllers. They did this while they were diagnosing a fault with the water system and the pumps. Therefore, this visit was to...
by Maximus Chillers | Mar 5, 2020 | Chilling Plant
We recently carried out R134a chilling plant maintenance at our customer’s factory in the North West. The chiller is 600kw with 2 single compressor systems. It has an ‘in house’ controller on it with occasional spurious trip outs. We are working with the problem so...
by Maximus Chillers | Sep 19, 2019 | Chilling Plant
Chilling plant service had been arranged because our customer had been having high pressure problems. Transducer required Chilling Plant Service The 4-20mA transducer needed replacing as it was reading low by a long shot. Therefore, the PLC was not bringing the fans...