by Maximus Chillers | Nov 22, 2022 | Articles
An ammonia chiller had been found to need an evaporator repair on a previous call out. The water Inlet and Outlet to the plate evaporator had been valved off and then it had been drained down. This was to stop any further leaking of water into the refrigerant system....
by Maximus Chillers | Aug 1, 2022 | Water Chillers
A water chiller repair visit to rectify the non condensables which were discovered in a refrigerant system. This condition happens when a system is purged through with refrigerant. Carrying out this procedure does not remove the air from the complicated internal...
by Maximus Chillers | Jun 19, 2022 | Articles
An industrial chiller repair service had been arranged to replace one of the compressors on System 1. Read on for a detailed insight into how we do things here at Maximus Chillers… News Article No.28 During the last maintenance visit, the engineer in the photo had...
by Maximus Chillers | Apr 24, 2022 | Articles
We at Maximus Chillers have just carried out a process chiller repair service for a customer of ours in the North West. The expansion valve on System 1 had been found to have failed and this was the return visit to rectify. There is N+1 redundancy built into the...
by Maximus Chillers | Dec 10, 2021 | Overseas Customers
North Sea Offshore & Marine Chiller Service On a previous visit for offshore & marine chiller service on an oil rig, our customer had shown us to a large air cooled chiller. His complaint was that it was tripping out all the time when there was nothing wrong...